Plan Review Notes
Plan Review Notes For Permit 08010430
Permit Number 08010430
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-18 15:21:13 
  
 ** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE LIGHTING IN BATHROOM NEEDS TO MEET
 410.8 TO BE OUTSIDE SHOWER AREA OR MEETING THE
 EXCEPTIONS FOR HEIGHT/CLEARANCE REQUIREMENTS ALONG WITH
 CLOSED IN TYPE OF FIXTURES FOR SHOWER LOCATIONS.
 AS THIS AREA ALL APPEARS TO BE A SHOWER, THESE WILL BE
 REQUIRED TO BE RATED FOR SUCH LOCATIONS.
 110.3, 410.8 ETC
  
 2) NOTE: PLEASE CLARIFY RECEPTACLE SPACING ALONG
 KITCHEN COUNTER SPACES PER 210.52C1. IF NEW CABINETS,
 COUNTERS AND WALL AREAS ARE DONE, SPACING SHALL MEET
 CURRENT CODE.
  
 3) NOTE: PLEASE SEE NEW SWITCH IN DINING ROOM WHICH
 DOES NOT SHOW WHAT IS WILL BE CONTROLLING.
 PLEASE SHOW. 210.70
  
 4) NOTE: PLEASE PROVIDE PANEL SCHEDULE WITH THE MINIMUM
 NEW CIRCUITS BEING PROPOSED. FOR EXAMPLE: EXISTING
 PLANS DID NOT SHOW BATH ROOM CIRCUIT, YET NEW SHOW NEW
 GFI.
 PLEASE SEE 210.11C3 FOR REQUIRED DEDICATED 20AMP AND
 #12 BRANCH CIRCUITS.
 310.16, 408.4, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLANS INDICATE NEW DOOR OPENERS YET NO NEW
 ELECTRICAL IS BEING SHOWN FOR THESE SAME LOCATIONS.
 PLEASE COMPLETE INFORMATION.
 310.16, 240.4, ETC
  
 6) NOTE: PLEASE SEE THE EXISTING UTILITY ROOM IS NOW
 BEING SHOWN AND WILL BE CONSIDERED AN ADAPTABLE
 SLEEPING ROOM PER NFPA-72.
 PLEASE SEE AN ADDITIONAL SMOKE ALARMS (NOT DETECTORS)
 WILL BE REQUIRED INSIDE AND OUTSIDE THIS ROOM.
 11.5.1.1.1
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]