| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS |
| | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | 1} PROVIDE A RISER DIAGRAM PER 215.5 INCLUDING |
| | GENERATOR AND RELATED EQUIPMENT. |
| | |
| | 2} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING |
| | RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE |
| | GENERATOR AND TRANSFER SWITCH.THREE MODELS ARE ON THE |
| | SPEC SHEET SUBMITTED. |
| | |
| | 3} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO |
| | BE SERVED. 215.5. 702.5, 2005NEC.702.5 CAPACITY AND |
| | RATING. AN OPTIONAL STANDBY SYSTEM SHALL HAVE ADEQUATE |
| | CAPACITY AND RATING FOR THE SUPPLY OF ALL EQUIPMENT |
| | INTENDED TO BE OPERATED AT ONE TIME. |
| | |
| | 4} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL. |
| | 106.3.5.4 FBC AS AMENDED. |
| | |
| | 5} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON |
| | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, |
| | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW |
| | PER 106.1 FBC AS AMENDED. THE PERSON TAKING |
| | RESPONSIBILITY FOR THE DESIGN MUST PRINT AND SIGN THEIR |
| | NAME TO SAME, ALL SHEETS, PER 106.1.3.FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |