| 2008-03-11 16:17:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING |
| | CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL |
| | GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL GEN/RES |
| | INSPECTION. THE FOLLOWING INFORMATION IS REQUIRED FOR |
| | THE GAS PERMIT APPLICATION ON THE REQUIRED GAS |
| | ISOMETRIC RISER DIAGRAM. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. PER SECTION 401.1 SCOPE. |
| | **THIS INCLUDES THE EXISTING GAS SYSTEM. SEE PERMIT |
| | INFORMATION INDICATING EXISTING GAS TO SAID ADDRESS |
| | ATTACHED TO THESE COMMENTS. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS |
| | SECTION 401.1 SCOPE. |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL) PER FBC FUEL GAS |
| | SECTION 401.1 SCOPE. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE |
| | COMMENT #1. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE |
| | COMENT #1. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. LP GAS SPECIFY 10 |
| | PSI. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATION SHEETS FOR THE GENERATOR CLEARLY |
| | INDICATING THE MODEL NUMBER, BTU LOAD CAPACITY WITH |
| | GENERATOR RUNNING @ 100%, AND A LISTING FROM A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | NOTE: EXISTING GAS SYSTEM WAS LP/GAS, IF GAS TO |
| | PROPOSED GENERATOR IS ALSO LP/GAS PLEASE SUBMIT TWO |
| | COPIES OF MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| | REQUIRED 2ND STAGE REGULATOR CLEARLY INDICATING THE |
| | MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| | FROM A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | |
| | 8. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | **NOTE: IF TANK IS EXISTING, PLEASE INDICATE THAT IT |
| | IS EXISTING. |
| | |
| | 9. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | 10. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | END OF COMMENTS: |
| | |