| | BUILDING PLAN REVIEW |
| | PERMIT: 08010423 |
| | ADD: 1745 PINE HURST DR. |
| | CONT: HAI- TECH ELECTRIC LLC. |
| | TEL: (561)389-5343 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE |
| | ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF |
| | OVERTURNING, UPLIFT AND SLIDING. |
| | |
| | GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE |
| | SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE |
| | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| | REQUIRES WITHOUT LOAD REDUCTION. |
| | |
| | PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR |
| | VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE |
| | VENTS, ETC. |
| | |
| | 2) 1609.6.2 WIND DESIGN PROCEDURES |
| | 1)THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3.THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 3)PROVIDE TWO SETS OF DRAWINGS SHOWING THE LOCATION |
| | OF THE GENERATOR SLAB WITH ALL INFORMATION MENTIONED |
| | ABOVE. THE LENGTH WIDTH AND THICKNESS OF THE SLAB SHALL |
| | BE INDICATED ON THE DRAWINGS. IF THE DESIGN |
| | PROFESSIONAL IS AN ARCHITECT OR ENGINEER LEGALLY |
| | REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE |
| | PRACTICE OF ARCHITECTURE AS PROVIDED FOR IN CHAPTER |
| | 481, 471 FLORIDA STATUTES THEN HE OR SHE SHALL AFFIX |
| | HIS OR HER OFFICIAL SEAL, SIGNATURE AND DATE TO SAID |
| | DRAWINGS. THESE DRAWINGS SHALL CONTAIN THE ORIGINAL |
| | SIGNATURE OF THE PERSON SEALING THE DRAWINGS. |
| | |