| 2008-05-19 12:07:42 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTE WHICH |
| | REQUESTED THE MANUFACTURES SPECS/CUT SHEETS FOR THE NEW |
| | PROPOSED ATS TO BE SUBMITTED. THIS WAS INDEED DONE |
| | HOWEVER THE SUBMITTAL SPECS/CUT SHEETS DO NOT CORRELATE |
| | WITH THE SUBMITTED INFORMATION ON PLANS. THE PLANS CALL |
| | FOR SEPARATE EQUIPMENT, DIFFERENT MANUFACTURE ETC. |
| | 90.7, 110.9, 110.3 ETC. |
| | FBC 106.1.2. |
| | PLEASE KNOW AT THIS TIME WITH NO INSTALLATION OF A |
| | GENERATOR NO VIOLATION EXISTS HOWEVER PLEASE KNOW A |
| | DISCONNECTING MEANS FOR THE GENERATOR FEEDERS MAY BE |
| | REQUIRED AT THE FUTURE DATE. 225.34. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #5. PLANS NOW |
| | SHOW SMOKE DETECTORS HOWEVER NO HORN, STROBE DEVICES, |
| | OR OTHER LOW VOLTAGE FIRE ALARM DEVICES OR SYSTEMS ARE |
| | SHOWN. |
| | PLEASE SEE NFPA-72 AS THE DEFINITION OF A SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH *DETECTS* AND DOES NOT |
| | SOUND ANY ALARM. PLEASE SEE THE SAME CODE FOR |
| | DEFINITION OF *SMOKE ALARMS*.SMOKE ALARMS ARE DEVICES |
| | WHICH *DETECT* AND *SOUND* AN ALARM. |
| | ARE THESE DEVICES NOT SMOKE ALARMS? |
| | PLEASE SEE R313, 11.5.1.1, 11.8.3 NFPA-72 2003. |
| | PLEASE INDICATE IF NEW TO BE INSTALLED OR ALREADY |
| | EXISTING. |
| | |
| | 3) NOTE: PLEASE SEE THE LOADS ON THE SERVICE ARE |
| | REQUIRED TO BE FIGURED PER 220.83B. |
| | |
| | 4) NOTE: PLEASE SEE THE CU#2 IS BEING FED FROM NEW |
| | PANEL B YET THE AHU IS BEING FROM EXISTING PANEL *A*. |
| | WHEN UNDER FUTURE GENERATOR POWER ONLY HALF OF THIS |
| | SYSTEM WOULD BE UNDER POWER BEING FED FROM TWO |
| | SOURCES. |
| | ** THIS IS GIVEN AS INFORMATION ONLY HOWEVER MAY WANT |
| | TO REVISE AT THIS TIME. |
| | |
| | ** PLANS ARE COMING BACKFOR OTHER CORRECTIONS, PLEASE |
| | ADDRESS COMMENTS 1-3. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |