| 2008-01-28 14:34:08 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P-3 NATURAL GAS PIPING RISER: |
| | SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION *401.1 SCOPE. |
| | *THE GAS PIPING RISER DOES NOT INDICATE CORRESPONDING |
| | LENGTHS TO ALL CUT SECTIONS OF PIPE. REFERENCE THE RED |
| | CIRCLED CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW. |
| | |
| | 2. SHEET P-3 NATURAL GAS PIPING RISER: |
| | SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS |
| | SECTION *401.1 SCOPE. |
| | *THE GAS PIPING RISER DOES NOT INDICATE THE TYPE OF |
| | PIPING MATERIAL BEING USED. |
| | |
| | 3. SHEET P-3 NATURAL GAS PIPING RISER: |
| | SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | * THE ADDED SUM OF THE INDICATED CORRESPONDING LENGTHS |
| | TO CUT SECTIONS OF PIPING EQUALS 151', HOWEVER NOTES: |
| | 3) DISTANCE IS INDICATING 185'. PLANS AT A MINIMUM |
| | SHALL BE CORRELATED. PER FBC FUEL GAS SECTION *401.1 |
| | SCOPE. |
| | |
| | 4. SHEET P-3 NATURAL GAS PIPING RISER: |
| | INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | * NOTES: 4) DELIVERY PRESSURE PRESSURE IS BEING |
| | INDICATED AS 0.8 PSI. THIS INDICATED DELIVERY PRESSURE |
| | IS WRONG FOR NATURAL GAS. FLORIDA PUBLIC UTILTIES CO. |
| | HAS 0.5, 2 OR 5 PSI DELIVERY PRESSURE. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | *PLEASE SUBMIT TWO COPIES OF MANUFACTURER |
| | SPECIFICATIONS ON THE PROPOSED GENERATOR INDICATING THE |
| | MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| | FROM A NATIONALLY RECOGNIZED TESTING LABORATORY AS WELL |
| | AS INDICATING THE MANUFACTURER SETBACK RECOMMENDATIONS |
| | FROM STRUCTURES. |
| | |
| | 6. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY CLEARLY |
| | INDICATING THE LOCATION OF THE PROPOSED GENERATOR |
| | INDICATING A DIMENTIONS FROM PROPERTY LINES AND |
| | DISTANCES FROM STRUCTURES. (ZONING APPROVAL REQUIRED |
| | FOR PROPOSED GENERATOR LOCATION PRIOR TO GAS PERMIT |
| | BEING ISSUED) PER FBC FUEL GAS SECTION *401.1 SCOPE |
| | |
| | 7. SHEET P-1 GAS PLAN IS CLEARLY INDICATING WHERE THE |
| | UNDERGROUND GAS PIPING IS BENEATH THE PROPOSED |
| | BUILDING. PER FBC FUEL GAS SECTION *404.11 PIPING |
| | UNDERGROUND BENEATH BUILDINGS. |
| | PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS |
| | PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A |
| | CONDUIT OF WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE |
| | DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. SUCH |
| | CONDUIT SHALL EXTEND INTO AN OCCUPIABLE PORTION OF THE |
| | BUILDING AND, AT THE POINT WHERE THE CONDUIT TERMINATES |
| | IN THE BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE |
| | GAS PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE |
| | ENTRANCE OF ANY GAS LEAKAGE. WHERE THE END SEALING IS |
| | CAPABLE OF WITHSTANDING THE FULL PRESSURE OF THE GAS |
| | PIPE, THE CONDUIT SHALL BE DESIGNED FOR THE SAME |
| | PRESSURE AS THE PIPE. SUCH CONDUIT SHALL EXTEND NOT |
| | LESS THAN 4 INCHES (102 MM) OUTSIDE THE BUILDING, SHALL |
| | BE VENTED ABOVE GRADE TO THE OUTDOORS AND SHALL BE |
| | INSTALLED SO AS TO PREVENT THE ENTRANCE OF WATER AND |
| | INSECTS. THE CONDUIT SHALL BE PROTECTED FROM CORROSION |
| | IN ACCORDANCE WITH SECTION 404.8 . CLEARLY INDICATE |
| | THIS REQUIREMENT ON THE RESUBMITTAL. PER FBC FUEL GAS |
| | SECTION *401.1 SCOPE. |
| | |
| | 8. SHEET P-3 NATURAL GAS PIPING RISER: NOTES: 1) |
| | INDICATES THE FOLLOWING "CONTRACTOR TO SUBMIT A PROPER |
| | GAS PIPING LAYOUT WITH PERMIT APPLICATION". BY THE |
| | INDICATION OF THIS NOTE, IS IT THE INTENT TO HAVE THE |
| | PLUMBING OR GAS CONTRACTOR TO SUBMIT THEIR OWN DESIGN |
| | AT THE TIME OF THE GAS PERMIT APPLICATION? IF THAT IS |
| | THE INTENT PLEASE REMOVE ALL GAS PIPING DESIGN FROM |
| | SHEETS P-1 AND P-3 AS WELL AS THE PROPOSED GENERATOR |
| | AND CLEARLY INDICATE THE GENERATOR AS "FUTURE". PER |
| | CITY WPB AMENDMENTS SECTION *106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND SECTION *401.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |
| | |
| | |