| Date |
Text |
| 2008-01-23 15:33:55 | |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | ** PLANS SHOW THE 1999 NFPA-70 AND A 2004 NFPA/LS 101 |
| | WHICH DOES NOT EXIST. PLEASE ADJUST. |
| | PLEASE ALSO INCLUDE THE ABOVE RELEVANT CODES ON |
| | ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE SUBMIT THE RELEVANT MANUFACTURES |
| | SPECS/CUT SHEETS FOR THE NEW PROPOSED GENERATOR AND |
| | TRANSFER SWITCH. |
| | PLEASE BE SURE THE MANUFACTURES SPECS/CUT SHEETS |
| | CONTAIN ALL THE MINIMUM CLEARANCE REQUIREMENTS. 110.3, |
| | 90.7. |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 3) NOTE: PLEASE INDICATE IF THE GENERATOR WILL BE A |
| | SEPARATELY DERIVED SYSTEM. PLEASE SEE |
| | 250.20,250.66,250.30 ETC. |
| | PLEASE KNOW KOHLER AS STATED ON PLANS COME SHIPPED AS |
| | SD AND WILL REQUIRE REMOVAL OF BONDING JUMPER IF THIS |
| | IS NOT GOING TO BE SD. |
| | |
| | 4) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES FOR |
| | CU #2 AND #3, DISCONNECTS. |
| | |
| | 5) NOTE: PLEASE SEE FBC R313 FOR REQUIRED NEW OR |
| | EXISTING SMOKE ALARMS IN THE EXISTING DWELLING MEETING |
| | CURRENT NFPA-72 11.5.1.1, AND 11.8.3. |
| | PLEASE SHOW LAYOUT OF ALL NEW TO BE INSTALLED OR |
| | EXISTING MEETING CURRENT CODES. |
| | |
| | 6) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE, THE |
| | POOL SCOPE OF WORK WILL BE REQUIRED TO BE UNDER A |
| | SEPARATE PERMIT. |
| | 106.1 |
| | |
| | 7) NOTE: PLEASE CLARIFY HEATING SYSTEMS. LOAD |
| | CALCULATIONS INDICATE *SPACE HEATERS* HOWEVER SHOULD |
| | THESE NO BE HEAT-STRIPS? SPACE HEATERS BY DEFINITION |
| | ARE NOT THE SAME AS CENTRAL HEAT. |
| | PLEASE ADJUST. |
| | FBC 106.3.5.4, NEC 424, 422 |
| | |
| | 8) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52, |
| | 210.52H FOR FOYER/HALL AREA. PLEASE ALSO VERIFY WALL AT |
| | WHAT APPEARS TO BE HALL AREA #2 ON WALL SPACE ON THE |
| | BACK/UNDERSIDE OF COUNTER SPACE. |
| | |
| | 9) NOTE: PLEASE SEE 410.8 FOR MINIMUM CLEARANCES FOR |
| | LIGHTING FIXTURES. THE TYPE OF FIXTURE NEEDS TO BE |
| | RELOCATED OR ADJUST TYPE OF FIXTURE. |
| | |
| | 10) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE(S) FOR |
| | NEW CIRCUITS ARE TO BE SPECIFIC TO ROOMS AND AREAS IN |
| | WHICH THEY FEED. PLEASE SEE THE FOLLOWING TEXT WHICH IS |
| | TAKEN FROM THE CODE COMMENTARY. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | AS THE PANEL SCHEDULE MENTIONS GEN LTS AND RECEPTS IN |
| | MANY LOCATIONS, THESE WOULD BE FOR EXAMPLE: MEDIA ROOM, |
| | DINING RM LTS, DINING RM RECEPTS ETC. |
| | IT IS KNOWN TO THIS OFFICE THIS WILL BE REVISED BEFORE |
| | FINAL. |
| | FBC 106.1.2, 106.3.5.4, |
| | |
| | 11) NOTE: PLEASE SEE FOUNTAIN LOCATION AT REAR OF |
| | DWELLING WHICH IS SWITCHED FROM INSIDE DOES NOT SHOW |
| | ANY GFI PROTECTION AS REQUIRED PER 210.8A3, 680.56 |
| | |
| | 12) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM ALL LOCATIONS AFTER THE FIRST |
| | MEANS OF DISCONNECT PER 250.110, 250.24, 250.6, 250.122 |
| | ETC |
| | |
| | 13) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS FOR |
| | FEEDERS FROM GENERATOR TO DWELLING. |
| | PLEASE SEE 225.31-225.39. PLEASE ALSO SEE 702.11 AS THE |
| | EXCEPTION OF THE DISCONNECTING MEANSMSUT MEET ALL |
| | REQUIREMENTS. |
| | |
| | 14) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM IS |
| | SHOWING #4 AWG FOR GROUNDING ELECTRODE CONDUCTOR BEING |
| | PARALLELED WHICH IS NOT PERMITTED. PLEASE SEE 250.66 |
| | FOR SIZING OF THE GROUNDING ELECTRODE CONDUCTOR. PLEASE |
| | SEE THE RISER ALSO SHOW *STRUCTURAL STEEL* AS PART OF |
| | THE GROUNDING ELECTRODE SYSTEM. STRUCTURAL STEEL WHERE |
| | PRESENT IS REQUIRED PER 250.50, HOWEVER PLEASE SEE |
| | 250.50 AS FOOTER STEEL (NEW) IS ALSO REQUIRED. |
| | PLEASE ADJUST AND INCLUDE ON RISER. |
| | |
| | 15) NOTE: PLEASE SEE THE SERVICE IS BEING SHOWN AS |
| | 400AMPS YET THE METER CAN IS ONLY SHOWN AS 300AMPS. IS |
| | THIS A TRUE 300AMP METER CAN? |
| | PLEASE VERIFY AND ADJUST AS ALL SERVICE EQUIPMENT SHALL |
| | BE RATED FOR SIZING OF SERVICE. |
| | 110.3, 90.7, 230, ETC |
| | |
| | 16) NOTE: PLEASE VERIFY CIRCUITING FOR DINING ROOM |
| | RECEPTACLES PER 210.52B1, 210.11C1 AND 220.53. PLEASE |
| | SEE LOAD CALCULATIONS INDICATE 3-SMALL APPLIANCE |
| | CIRCUITS YET THE PANEL SCHEDULES ONLY SHOWS 2. PLEASE |
| | CLARIFY IF THIS OTHER CIRCUIT AS SHOWN IS THE DINING |
| | ROOM. |
| | |
| | 17) NOTE: PLEASE VERIFY THE KW RATING OF THE GENERATOR. |
| | THE UNIT IS 30KW ON RISER AND 27KW IN NOTES. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |