| Plan Review Notes For Permit 08010387 |
| Permit Number |
08010387 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-05-02 14:47:55 | *****PROVISO***** | | | | | | 1.SHOW THE LOCATION OF THE 2A10BC RATED FIRE | | | EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | 2.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS | | | AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | WHEN THE ABOVE ITEMS AS WELL AS THE OTHER REVIEWERS | | | COMMENTS HAVE BEEN ADDRESSED, THE APPROPIATE SHEETS TO | | | BE FIRE-STAMPED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|