| 2008-05-01 16:54:37 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 2B, 3.SHEET A2 WAS REVISED TO CORRECTLY STATE MIXED |
| | OCCUPANCY BUT SHEET A1 STILL STATES SINGLE OCCUPANCY |
| | MERCANTILE.PLEASE CORRELATE. |
| | |
| | 4-8. ADDRESSED. |
| | |
| | 9. ARCHITECT'S RESPONSE THAT LIGHT POLE CALCS WILL BE |
| | SUBMITTED IS ACKNOWLEDGED.THIS WILL BE A PROVISO |
| | ITEM. |
| | |
| | 10-13. ADDRESSED. |
| | |
| | 14. A5 AND ARCHITECT'S RESPONSE INDICATE THAT A NEW |
| | ROOF WILL BE INSTALLED.SEE SHEET A3, ROOF PLAN.ROOF |
| | DESIGN PRESSURES WERE DECLARED AS FOLLOWS; -27.4 FOR |
| | ZONE 1, -25 PSF FOR ZONE 2, -38.2 FOR ZONE 3.PROVIDE |
| | CALCULATIONS AS THESE PRESSURES ARE TOO LOW.ALSO |
| | EXPLAIN THE LOGIC OF A DESIGN PRESSURE LOWER IN ZONE 1 |
| | THAN ZONE 2.SEE FBC 1609. |
| | |
| | 15-17. ADDRESSED. |
| | |
| | 18.ENERGY CALCS SHOW 8187 SF OF CARPET WITH A RUBBER |
| | PAD, PLANS SHOW TILE.INSULATION ON THE ENERGY CALC |
| | FOR ROOF IS SHOWN AS 15.4, PLANS SHOW R12.WITH THE |
| | RESUBMITTAL, PROVIDE ROOF INSULATION SPECIFICATIONS |
| | SHOWING R VALUE AND MANUFACTURER. |
| | |
| | NEW COMMENTS: |
| | |
| | 19.OLD SHEETS AND ENERGY CALCS WERE NOT SUBMITTED. |
| | PLEASE PROVIDE.THEY ARE REQUIRED FOR REFERENCE. |
| | CHANGES TO THE PLAN SHOULD ALWAYS BE CLOUDED AND MARKED |
| | WITH A REVISION NUMBER AND OLD SHEETS SUBMITTED FOR |
| | REFERENCE, SEE FIRST CORRECTION LISTS (DEWEY PALMER AND |
| | JIM WITMER). |
| | |
| | 20.THE OCCUPANT LOAD INCLUDES ONLY THE SALES AREA. |
| | SEE FBC1004.1, OCCUPANT LOAD IS TO BE BASED ON THE |
| | GREATER OF DESIGN LOAD OR THE OCCUPANT LOAD BASED ON |
| | SQUARE FOOT AREA AND FBC TABLE 1004.1.2.REVISE |
| | OCCUPANT LOAD TO INCLUDE ENTIRE BUILDING. |
| | |
| | 21.MECHANICAL STANDS REQUIRE PRODUCT APPROVAL, |
| | FAC9B72, SEE SHEET A3. |
| | |
| | 22.8INCHES IS SPECIFIED FROM THE BOTTOM OF THE A/C |
| | UNIT TO THE ROOF.SEE FBC1509.7 AND REVISE |
| | ACCORDINGLY.INCLUDE DIMENSIONS OF THE UNIT.SHEET |
| | A3. |
| | |
| | 23.A STAND IS SHOWN ON SHEET A3 WHICH CONFLICTS WITH |
| | THE ROOF CURB SPECIFIED ON AC1.PLEASE CORRELATE. |