| 2008-03-10 10:34:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | |
| | 1. SEE ELECTRICAL REVIEW NOTES #2 AND #3 CONCERNING |
| | ENERGY CALCULATIONS, PLEASE CORRECT. ALSO THE NEW |
| | ELECTRIC WATER HEATER NEEDS TO COMPLY PER TABLE |
| | *13-412.1.ABC.3 AND HOT WATER PIPE INSULATION PER TABLE |
| | *611.1.ABC.1 ON THE RESUBMITTAL. |
| | |
| | **COMMENT RESPONSE NOTED FROM ARCHITECT TO SEE |
| | ENGINEERING, HOWEVER THERE IS NO COMMENT RESPONSE FROM |
| | ENGINEERING FOR PLUMBING. COMMENT WAS NOT ADDRESSED. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | |
| | 3. SHEET P-1 WASTE RISER AND PARTIAL PLUMBING PLAN: |
| | WATER CLOSETS REQUIRE A VENT. PER FBC PLUMBING, SECTION |
| | *901.2.1 VENTING REQUIRED. |
| | |
| | **COMMENT RESPONSE NOTED FROM ARCHITECT TO SEE |
| | ENGINEERING, HOWEVER THERE IS NO COMMENT RESPONSE FROM |
| | ENGINEERING FOR PLUMBING. COMMENT WAS NOT ADDRESSED. |
| | |
| | 4. *NEW COMMENT* SHEET P-2 DETAIL A, THE WATER HEATER |
| | NEEDS PROTECTION FROM THERMAL EXPANSION CONTROL. PER |
| | FBC PLUMBING SECTION 607.3 AND 607.3.2 . |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |