| 2008-03-17 08:52:48 | ** DENIED2ND REVIEW** |
| | |
| | ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT |
| | TO RELEVANT CODES. PLEASE SEE SHEET A-2 WHICH STATES A |
| | 2004 NFPA-70. |
| | PLEASE SEE FBC 2004W/2007 WHICH ADOPTS THE 2005 |
| | NFPA-70. |
| | PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | ARE NOT AN ADOPTED VERSION PER FBC 13-400.3.B. THIS WAS |
| | CONFIRMED PREVIOUSLY WITH MO MADANI FROM DEPARTMENT OF |
| | COMMUNITY AFFAIRS THAT ONLY THE VERSION AS STATED IN |
| | SECTION NOTED IS ACCEPTABLE WHICH IS 2.5. |
| | |
| | 3) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WHICH |
| | CONTAINS A RAISED SEAL OVER A PHOTO-COPIED SIGNATURE |
| | WHICH IS NOT PERMITTED BY FS 481.221. |
| | PLEASE SEE THE PREVIOUS REVIEW STATED TO SUBMIT SIGNED |
| | AND SEALED AS REQUIRED. |
| | **MAY NOT PLACE A RAISED SEAL OVER PHOTO-COPIED |
| | SIGNATURE. ONE SET HAS BEEN RETAINED BY THIS OFFICE. |
| | |
| | 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | DO NOT CORRELATE WITH PLANS. |
| | A) PLEASE SEE CONTROLS ARE NOTED AS *MANUAL ON/OFF * |
| | WHICH IS NOT POSSIBLE WHEN PLANS SHOW AUTOMATED |
| | CONTROLS |
| | B) PLEASE SEE THE WATTAGE ON FIXTURES ON CALCULATIONS |
| | DO NOT CORRELATE WITH THE FIXTURES ON FIXTURE LEGEND OR |
| | THE COUNT OF FIXTURES ON PLANS. |
| | FOR EXAMPLE: PLEASE SEE FIXTURES B AND BE WHICH ARE |
| | NOTED MODEL WITH 2-32 BULBS YET THE NUMBER OF LAMPS ARE |
| | NOTED AS 4-32W? IN EITHER CASE THESE DO NOT CORRELATE. |
| | FOR EXAMPLE: THE IDR NOTES 5-51W FIXTURES IN SALES AREA |
| | YET ONLY TWO TYPE *B* FIXTURES ARE LOCATED IN THIS |
| | SPACE. |
| | C) PLEASE SUBMIT FIXTURE INFORMATION/SPEC SHEET FOR |
| | PROPOSED FIXTURES.THIS OFFICE IS AWARE OF BALLAST |
| | EFFICIENCIES HOWEVER COULD NOT LOCATE THE MODEL AS |
| | NOTED. |
| | D) PLEASE SEE THE IDR AS THERE IS NOT WATER HEATER |
| | SHOWN, HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW |
| | ELECTRICAL WATER HEATER? 13-412.1.ABC.3.4 |
| | PLEASE GO OVER ALL LIGHTING AND BE SURE THE IDR |
| | COORDINATES WITH THE PLANS. |
| | 13-415.1.B, 13-415.2 ETC |
| | |
| | 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS PERFORMANCE |
| | INFORMATION ON SHEET E-4 SHOWS A RETAIL VALUE OF 1.5, |
| | HOWEVER PLEASE SEE 2004 FBC WITH CURRENT SUPPLEMENTS |
| | WHICH 13-415.2.B WHICH SHOWS 1.7 FOR RETAIL. |
| | PLEASE ADJUST. |
| | |
| | 6) NOTE: PLEASE SEE FEEDER SCHEDULE SHOWS *EQUIPMENT |
| | GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS OF |
| | DISCONNECT FOR ALL THREE MAINS WHICH IS NOT PERMITTED. |
| | 250.6, 250.24. |
| | PLEASE REMOVE. |
| | |
| | 7) NOTE: PLEASE CORRELATE SERVICE ENTRANCE CONDUCTORS |
| | FOR MAIN PANEL *A* WHICH SHOWS 3/0 ON PANEL AND 4/0 ON |
| | RISER CONDUCTOR SCHEDULE. |
| | |
| | 8) NOTE: PLEASE PROVIDE MORE DETAIL FOR LIGHTING |
| | CONTROLS. |
| | A) PLEASE SEE THE EXTERIOR LIGHTS ARE NOTED ON A TIME |
| | CLOCK HOWEVER IS THIS AN ASTRONOMICAL TIME CLOCK WITH |
| | 10HR MINIMUM BACK UP? 13-415.1.ABC.1.4 |
| | B) PLEASE VERIFY THE STANDARD SP SWITCH IN WAREHOUSE |
| | WHICH IS REQUIRED TO BE AN OVER RIDE PER |
| | 13-415.1.ABC.1.1, .1.2. |
| | HOW DOES THIS SP WORK AS AN OVER RIDE? |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |