| 2008-04-04 10:28:45 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 2B, MERCANTILE SINGLE OCCUPANCY DECLARED.SEE ALSO |
| | ITEM 3 FROM THE PREVIOUS LIST.THIS IS A MIXED USE AND |
| | MUST BE DECLARED AS SUCH AS THE WAREHOUSE (S1) AREA IS |
| | OVER 10%, FBC302.2. |
| | |
| | THE 1 HOUR WALL IS SHOWN, BUT NO FIRE RESISTANCE RATING |
| | REQUIREMENTS ARE SHOWN FOR THE DOORS IN THE 1 HOUR |
| | OCCUPANCY SEPARATION WALL.PLEASE STATE DESIGN |
| | CRITERIA, FBC715.3. |
| | |
| | 3. DECLARE MIXED USE AS THE S1 AREA IS NOT LESS THAN |
| | 10% OF THE STORY, FBC302.2. |
| | |
| | 4. THE RESPONSE LETTER STATES THAT THERE IS NO STORAGE |
| | OF HAZARDOUS MATERIALS.PLEASE NOTE ON THE PLAN. |
| | |
| | 5.THE FIRST COMMENT LIST STATED ?THE PLANS INDICATE |
| | THIS IS TO BE A MERCANTILE TYPE BUSINESS BUT THERE IS |
| | NOT INFORMATION ON THE INTERIOR TO INDICATE COMPLIANCE |
| | WITH 11-7, PLANS ARE NOT COMPLETE.?ARCHITECT?S |
| | RESPONSE WAS ?ALL ITEMS SHOWN ON PLAN ARE CASEWORK AND |
| | RACKS FOR CLOTHES, TOYS, NOVELTIES, ETC.?IF THIS IS A |
| | DOLLAR STORE AS STATE, THERE SHOULD BE A PLACE FOR |
| | CHECKOUT.PLEASE SEE FBC11-7 AND SHOW COMPLIANCE WITH |
| | ALL REQUIREMENTS ON THE PLAN. |
| | |
| | 6-8. ADDRESSED OR INCLUDED IN OTHER COMMENTS. |
| | |
| | 9. ARCHITECT?S RESPONSE THAT LIGHT POLE CALCS WILL BE |
| | SUBMITTED IS ACKNOWLEDGED.THIS WILL BE A PROVISO |
| | ITEM. |
| | |
| | NEW COMMENTS: |
| | |
| | 10. AS DRAWN, THE DUMPSTER GATE ENCROACHES THE PROPERTY |
| | LINE WHEN IN THE FULLY OPEN POSITION.SEE FBC3202.2. |
| | |
| | 11. THE 1 HOUR PARTITION DETAIL ON A5 DOES NOT SHOW THE |
| | NEW CEILING.SIGNAGE REQUIRED ABOVE THE CEILING, |
| | FBC712.5. |
| | |
| | 12. ONE AISLE SHOWS A COLUMN IN THE MIDDLE, SEE |
| | FBC11-4.3.3.OTHER AISLES SHOW A COLUMN IN THE AISLE, |
| | BUT DOES NOT PROVIDE A DIMENSION SHOWING DISTANCE FROM |
| | THE SHELF.IT IS NOT CLEAR WHETHER THE 36IN MINIMUM IS |
| | MET.WITH THE EXCEPTION OF THE COLUMN IN THE MIDDLE OF |
| | THE AISLE, THIS COMMENT CAN BE ADDRESSED WITH A GENERAL |
| | NOTE. |
| | |
| | 13. SEE F1, LEFT SIDE OF PLAN, CENTER.THE AREA WHICH |
| | APPEARS TO BE THE CASHIER AREA IS TO BE DESIGNED SO |
| | THAT INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, |
| | AND EXIT THE WORK AREA.SEE FBC11-4.1.1(3), |
| | FBC11-4.1.6(1)(B). |
| | |
| | 14. ROOF PRODUCT APPROVALS SUBMITTED.PLEASE CLARIFY, |
| | PREFERABLY ON THE ROOF FRAMING PLAN WHERE ROOF WORK |
| | WILL BE DONE. DETAIL 8S3 SHOWS EXISTING ROOF DECK TO |
| | REMAIN.THE ROOF PRODUCT APPROVAL IS INCOMPLETE, LAST |
| | PAGE REQUIRED TO DETERMINE LIMITATIONS.ENHANCED |
| | FASTENING NOT SUBMITTED.THIS MAY BE DONE BY THE |
| | ROOFING CONTRACTOR AT THE TIME OF ROOF PERMIT |
| | APPLICATION, BUT FIRST PLEASE CLARIFY ROOF WORK TO BE |
| | PERFORMED UNDER THE SCOPE OF THIS PERMIT. |
| | |
| | 15. SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, |
| | FBC13-103.1. |
| | |
| | 16. SEE SHEET AC1, NO FIRE DAMPERS SHOWN AT PENETRATION |
| | THROUGH THE RATED WALL, FBC712. |
| | |
| | 17. SHOW REQUIRED DETECTABLE WARNINGS, FBC11-4.29.5. |
| | |
| | 18.THE DOORS ON THE ENERGY CALCS DO NOT MATCH THE |
| | PLAN.PLEASE CONFIRM ALL BUILDING COMPONENTS AS I ONLY |
| | SPOT CHECK ENERGY CALCS.THIS MAY NOT BE AN EXHAUSTIVE |
| | LIST. |