2008-04-04 10:28:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 2B, MERCANTILE SINGLE OCCUPANCY DECLARED.SEE ALSO
 ITEM 3 FROM THE PREVIOUS LIST.THIS IS A MIXED USE AND
 MUST BE DECLARED AS SUCH AS THE WAREHOUSE (S1) AREA IS
 OVER 10%, FBC302.2.
  
 THE 1 HOUR WALL IS SHOWN, BUT NO FIRE RESISTANCE RATING
 REQUIREMENTS ARE SHOWN FOR THE DOORS IN THE 1 HOUR
 OCCUPANCY SEPARATION WALL.PLEASE STATE DESIGN
 CRITERIA, FBC715.3.
  
 3. DECLARE MIXED USE AS THE S1 AREA IS NOT LESS THAN
 10% OF THE STORY, FBC302.2.
  
 4. THE RESPONSE LETTER STATES THAT THERE IS NO STORAGE
 OF HAZARDOUS MATERIALS.PLEASE NOTE ON THE PLAN.
  
 5.THE FIRST COMMENT LIST STATED ?THE PLANS INDICATE
 THIS IS TO BE A MERCANTILE TYPE BUSINESS BUT THERE IS
 NOT INFORMATION ON THE INTERIOR TO INDICATE COMPLIANCE
 WITH 11-7, PLANS ARE NOT COMPLETE.?ARCHITECT?S
 RESPONSE WAS ?ALL ITEMS SHOWN ON PLAN ARE CASEWORK AND
 RACKS FOR CLOTHES, TOYS, NOVELTIES, ETC.?IF THIS IS A
 DOLLAR STORE AS STATE, THERE SHOULD BE A PLACE FOR
 CHECKOUT.PLEASE SEE FBC11-7 AND SHOW COMPLIANCE WITH
 ALL REQUIREMENTS ON THE PLAN.
  
 6-8. ADDRESSED OR INCLUDED IN OTHER COMMENTS.
  
 9. ARCHITECT?S RESPONSE THAT LIGHT POLE CALCS WILL BE
 SUBMITTED IS ACKNOWLEDGED.THIS WILL BE A PROVISO
 ITEM.
  
 NEW COMMENTS:
  
 10. AS DRAWN, THE DUMPSTER GATE ENCROACHES THE PROPERTY
 LINE WHEN IN THE FULLY OPEN POSITION.SEE FBC3202.2.
  
 11. THE 1 HOUR PARTITION DETAIL ON A5 DOES NOT SHOW THE
 NEW CEILING.SIGNAGE REQUIRED ABOVE THE CEILING,
 FBC712.5.
  
 12. ONE AISLE SHOWS A COLUMN IN THE MIDDLE, SEE
 FBC11-4.3.3.OTHER AISLES SHOW A COLUMN IN THE AISLE,
 BUT DOES NOT PROVIDE A DIMENSION SHOWING DISTANCE FROM
 THE SHELF.IT IS NOT CLEAR WHETHER THE 36IN MINIMUM IS
 MET.WITH THE EXCEPTION OF THE COLUMN IN THE MIDDLE OF
 THE AISLE, THIS COMMENT CAN BE ADDRESSED WITH A GENERAL
 NOTE.
  
 13. SEE F1, LEFT SIDE OF PLAN, CENTER.THE AREA WHICH
 APPEARS TO BE THE CASHIER AREA IS TO BE DESIGNED SO
 THAT INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER,
 AND EXIT THE WORK AREA.SEE FBC11-4.1.1(3),
 FBC11-4.1.6(1)(B).
  
 14. ROOF PRODUCT APPROVALS SUBMITTED.PLEASE CLARIFY,
 PREFERABLY ON THE ROOF FRAMING PLAN WHERE ROOF WORK
 WILL BE DONE. DETAIL 8S3 SHOWS EXISTING ROOF DECK TO
 REMAIN.THE ROOF PRODUCT APPROVAL IS INCOMPLETE, LAST
 PAGE REQUIRED TO DETERMINE LIMITATIONS.ENHANCED
 FASTENING NOT SUBMITTED.THIS MAY BE DONE BY THE
 ROOFING CONTRACTOR AT THE TIME OF ROOF PERMIT
 APPLICATION, BUT FIRST PLEASE CLARIFY ROOF WORK TO BE
 PERFORMED UNDER THE SCOPE OF THIS PERMIT.
  
 15. SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 16. SEE SHEET AC1, NO FIRE DAMPERS SHOWN AT PENETRATION
 THROUGH THE RATED WALL, FBC712.
  
 17. SHOW REQUIRED DETECTABLE WARNINGS, FBC11-4.29.5.
  
 18.THE DOORS ON THE ENERGY CALCS DO NOT MATCH THE
 PLAN.PLEASE CONFIRM ALL BUILDING COMPONENTS AS I ONLY
 SPOT CHECK ENERGY CALCS.THIS MAY NOT BE AN EXHAUSTIVE
 LIST.