| Date |
Text |
| 2008-02-12 13:38:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SEE ELECTRICAL REVIEW NOTES #2 AND #3 CONCERNING |
| | ENERGY CALCULATIONS, PLEASE CORRECT. ALSO THE NEW |
| | ELECTRIC WATER HEATER NEEDS TO COMPLY PER TABLE |
| | *13-612.1.ABC.3.2 AND HOT WATER PIPE INSULATION PER |
| | TABLE *611.1.ABC.1 ON THE RESUBMITTAL. |
| | |
| | 2. SHEET A-2 TYPICAL ADA TOILET: AN ELEVATION DETAIL |
| | OF THE FOLLOWING FIXTURES IS REQUIRED COMPLIANT WITH |
| | CHAPTER 11, FLORIDA ACCESSIBILITY CODE WITH THE |
| | FOLLOWING INFORMATION. |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| | OF THE FRONT OF FOUNTAIN. |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH |
| | THE FOLLOWING INFORMATION) |
| | 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3 |
| | HEIGHT. 17" TO 19". |
| | 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C |
| | 36" LONG. |
| | 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" |
| | HIGH. |
| | 11-4.16.6 DISPENSERS. SEE FIGURE 29(B). |
| | |
| | **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| | REQUIRED WITH THE FOLLOWING INFORMATION) |
| | 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR |
| | COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE |
| | FIGURE 31) |
| | 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND |
| | A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| | 32) |
| | 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO |
| | PROTECT AGAINST CONTACT. |
| | 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| | ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| | 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F. |
| | |
| | 3. SHEET P-1 WASTE RISER AND PARTIAL PLUMBING PLAN: |
| | WATER CLOSETS REQUIRE A VENT. PER FBC PLUMBING, SECTION |
| | *901.2.1 VENTING REQUIRED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |