| 2008-02-22 10:07:26 | ***DENIED*** | | | | | | 1) DOORS PROVIDED WITH PANIC HARDWARE SHALL NOT BE | | | EQUIPPED WITH ANY LOCKING DEVICE THAT PREVENTS RELEASE | | | OF THE LATCH FROM THE EGRESS SIDE. NFPA 101, SECTION | | | 7.2.1.7.3. | | | | | | 2) IN ADDITION TO THE HEIGHT REQUIREMENT, ADDRESS | | | CHARACTERS SHALL BE MINIMUM OF 1" IN WIDTH AND | | | CONTRASTING WITH THE BACKGROUND FOR VISIBILITY. SHT | | | A-3 | | | | | | 3) CLEARLY IDENTIFY THE LOCATIONS OF EMERGENCY LIGHTING | | | FACILITIES THAT ARE REQUIRED. | | | | | | 4) EXIT SIGNS SHALL NOT BE GREATER THAN 100' APART AND | | | ARE TO BE VISIBLE AND OBVIOUS FROM ALL POINTS OF THE | | | MEANS OF EGRESS.. | | | | | | 5) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 6) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|