Plan Review Notes
Plan Review Notes For Permit 08010387
Permit Number 08010387
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-02-22 10:07:26***DENIED***
  
 1) DOORS PROVIDED WITH PANIC HARDWARE SHALL NOT BE
 EQUIPPED WITH ANY LOCKING DEVICE THAT PREVENTS RELEASE
 OF THE LATCH FROM THE EGRESS SIDE. NFPA 101, SECTION
 7.2.1.7.3.
  
 2) IN ADDITION TO THE HEIGHT REQUIREMENT, ADDRESS
 CHARACTERS SHALL BE MINIMUM OF 1" IN WIDTH AND
 CONTRASTING WITH THE BACKGROUND FOR VISIBILITY. SHT
 A-3
  
 3) CLEARLY IDENTIFY THE LOCATIONS OF EMERGENCY LIGHTING
 FACILITIES THAT ARE REQUIRED.
  
 4) EXIT SIGNS SHALL NOT BE GREATER THAN 100' APART AND
 ARE TO BE VISIBLE AND OBVIOUS FROM ALL POINTS OF THE
 MEANS OF EGRESS..
  
 5) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 6) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756