Plan Review Notes
Plan Review Notes For Permit 08010387
Permit Number 08010387
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-24 15:32:17 
  
 ** DENIEDREVIEW **
  
  
 ** PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN THE
 LEFT HAND SIDE OF PLANS.
 THESE SHOULD BE PLACED INTO SEPARATE FOLDERS/BINDERS OR
 SOME OTHER FASHION.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE
 PLACED ON ELECTRICAL PLANS FOR RELEVANT DESIGN.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70 (DONE)
 2003 NFPA-101
 2002 NFPA-72 (WHEN APPLICABLE).
  
 2) NOTE: PLEASE SEE THE REQUIRED ENERGY CALCULATIONS
 SUBMITTED ARE NOT SIGNED, DATED OR SEALED ON
 CERTIFICATION SHEETS AS REQUIRED PER FBC 13-103.1.1.1,
 FAC 61G15-23.002, FS 481.221, FS 471.025.
 PLEASE SEE THE SETS SUBMITTED ARE PHOTO-COPIES.
  
 3) NOTE: PLEASE SUBMIT INFORMATION ON HOW THE METHOD
 *A* IS BEING USED ON AN EXISTING BUILDING WHICH MEETS
 THE DEFINITION OF RENOVATIONS PER 13-101.1.3.
 THE CODE REQUIRES *B* OR *C*.
 PLEASE BE SURE ALL LIGHTING AS SHOWN ON PLANS
 COORDINATES WITH THE ELECTRICAL ON THE INPUT DATA
 REPORT.
  
 4) NOTE:PLEASE BE SURE ALL LIGHT FIXTURES SHOWN ON
 PLANS CONTAIN FIXTURE DESIGNATIONS.FOR EXAMPLE:
 PLEASE SEE REAR WAREHOUSE AREA WHICH SEEMS NOT TO SHOW
 ANY FIXTURE DESIGNATIONS.
 PLEASE CLARIFY HOW THE WATTAGE ON INPUT DATA REPORT
 SHOWS VA AT 102 FOR FIXTURES WITH 4-32W BULBS. PLEASE
 CONFIRM THE BALLAST/OUTPUT VA A RATING IS BEING USED AS
 REQUIRED PER 13-415.2.ABC.1.2
 PLEASE SEE MANY OF THESE FIXTURES ON IDR INDICATE
 COMPACT FLUORESCENT HOWEVER BASED ON FIXTURE LEGEND
 THIS IS NOT THE CASE.
 PLEASE BE SURE TO COORDINATE ALL.
 13-415.2
  
 5) NOTE: PLEASE SUBMIT ANY WIND LOAD CALCULATIONS FOR
 BUILDING REVIEW FOR OUTDOOR LIGHT POLES. PLEASE BE SURE
 THE EFFECTIVE PROJECTED AREA (EPA) IS SHOWN FOR
 PROPOSED FIXTURES.
 THIS IS ONLY NOTED AS THIS WILL BE PART OF BUILDING
 REVIEW.
  
 6) NOTE:PLEASE VERIFY THE GROUNDING ELECTRODES AS
 SHOWN ON PLANS.
 PLEASE SEE RISER SHOWS *STRUCTURAL STEEL* AS ON OF THE
 GROUNDING ELECTRODES. IF SHOWN, THEN THIS WILL BE
 REQUIRED.
 250.50
  
 7) NOTE: PLEASE SEE RISER NEEDS TO LABEL AND INDICATE
 ALL MAINS PER 230.2E (MAIN 1OF 3, 2 OF 3 ETC
  
 8) NOTE: PLEASE SEE 230.72 AS ALL MAINS ARE REQUIRED TO
 BE GROUPED. PLANS ONLY SHOW THE LOCATION OF THE PANEL
 *A* AND *B*. RISER SHOWS A/C MAINS BEING NEMA 3R WHICH
 IS BEING *ASSUMED* AS BEING OUTSIDE AND SHOWS PANEL *A*
 AS BEING NEMA 1 WHICH IS AN INDOOR RATED PIECE OF
 EQUIPMENT. THIS WOULD LEND TO THE FACT MAINS ARE NOT
 GROUPED AS NEEDED.
 PLEASE ALSO SEE POWER PLANS DO NOT SHOW LOCATIONS.
 240.24, 110.26, 230.72 ETC
 FBC ADMIN SECTION 106.3.5.1.2
  
 9) NOTE: PLEASE SEE RISER SHOWS MAIN ON PANEL *A* AS
 225AMPS, YET THE PANEL SCHEDULE ONLY SHOWS 200AMPS MAIN
 CIRCUIT BREAKER.
 PLEASE ALSO SEE THE SERVICE ENTRANCE CONDUCTORS FOR
 THIS SAME PANEL IS NOTED AS FEEDERS WHICH CAN NOTBE.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ON PANEL *A*
 SCHEDULE SHOWS 3/0 WHICH ARE ONLY RATED FOR 200AMPS PER
 310.16, 110.14, 240.4 AND THE RISER SHOWS 4/0.
 PLEASE KNOW IF THE MAIN IS GOING TO BE 225AMPS, THE 4/0
 CONDUCTOR ARE RATED.
 PLEASE COORDINATE ALL OF THE ABOVE.
 240.4, 230.70, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.2 ADMIN SECTION.
  
 10) NOTE: PLEASE SEE ALL CONDUITS TAPPED FROM THE
 GUTTER INDICATING AN EQUIPMENT GROUNDING CONDUCTOR
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED.
 PLEASE SEE 250.6, 250.24 AS THIS WOULD CREATE
 OBJECTIONABLE CURRENTS.
  
 ** PLEASE KNOW AS SOME INFORMATION WILL CHANGE, REVIEW
 FOR ALL ITEMS CAN NOT BE DONE AT THIS TIME.
 CHANGES MAY GENERATE NEW COMMENTS.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  