| 2008-01-24 15:32:17 | |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | |
| | ** PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN THE |
| | LEFT HAND SIDE OF PLANS. |
| | THESE SHOULD BE PLACED INTO SEPARATE FOLDERS/BINDERS OR |
| | SOME OTHER FASHION. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE |
| | PLACED ON ELECTRICAL PLANS FOR RELEVANT DESIGN. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 (DONE) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (WHEN APPLICABLE). |
| | |
| | 2) NOTE: PLEASE SEE THE REQUIRED ENERGY CALCULATIONS |
| | SUBMITTED ARE NOT SIGNED, DATED OR SEALED ON |
| | CERTIFICATION SHEETS AS REQUIRED PER FBC 13-103.1.1.1, |
| | FAC 61G15-23.002, FS 481.221, FS 471.025. |
| | PLEASE SEE THE SETS SUBMITTED ARE PHOTO-COPIES. |
| | |
| | 3) NOTE: PLEASE SUBMIT INFORMATION ON HOW THE METHOD |
| | *A* IS BEING USED ON AN EXISTING BUILDING WHICH MEETS |
| | THE DEFINITION OF RENOVATIONS PER 13-101.1.3. |
| | THE CODE REQUIRES *B* OR *C*. |
| | PLEASE BE SURE ALL LIGHTING AS SHOWN ON PLANS |
| | COORDINATES WITH THE ELECTRICAL ON THE INPUT DATA |
| | REPORT. |
| | |
| | 4) NOTE:PLEASE BE SURE ALL LIGHT FIXTURES SHOWN ON |
| | PLANS CONTAIN FIXTURE DESIGNATIONS.FOR EXAMPLE: |
| | PLEASE SEE REAR WAREHOUSE AREA WHICH SEEMS NOT TO SHOW |
| | ANY FIXTURE DESIGNATIONS. |
| | PLEASE CLARIFY HOW THE WATTAGE ON INPUT DATA REPORT |
| | SHOWS VA AT 102 FOR FIXTURES WITH 4-32W BULBS. PLEASE |
| | CONFIRM THE BALLAST/OUTPUT VA A RATING IS BEING USED AS |
| | REQUIRED PER 13-415.2.ABC.1.2 |
| | PLEASE SEE MANY OF THESE FIXTURES ON IDR INDICATE |
| | COMPACT FLUORESCENT HOWEVER BASED ON FIXTURE LEGEND |
| | THIS IS NOT THE CASE. |
| | PLEASE BE SURE TO COORDINATE ALL. |
| | 13-415.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT ANY WIND LOAD CALCULATIONS FOR |
| | BUILDING REVIEW FOR OUTDOOR LIGHT POLES. PLEASE BE SURE |
| | THE EFFECTIVE PROJECTED AREA (EPA) IS SHOWN FOR |
| | PROPOSED FIXTURES. |
| | THIS IS ONLY NOTED AS THIS WILL BE PART OF BUILDING |
| | REVIEW. |
| | |
| | 6) NOTE:PLEASE VERIFY THE GROUNDING ELECTRODES AS |
| | SHOWN ON PLANS. |
| | PLEASE SEE RISER SHOWS *STRUCTURAL STEEL* AS ON OF THE |
| | GROUNDING ELECTRODES. IF SHOWN, THEN THIS WILL BE |
| | REQUIRED. |
| | 250.50 |
| | |
| | 7) NOTE: PLEASE SEE RISER NEEDS TO LABEL AND INDICATE |
| | ALL MAINS PER 230.2E (MAIN 1OF 3, 2 OF 3 ETC |
| | |
| | 8) NOTE: PLEASE SEE 230.72 AS ALL MAINS ARE REQUIRED TO |
| | BE GROUPED. PLANS ONLY SHOW THE LOCATION OF THE PANEL |
| | *A* AND *B*. RISER SHOWS A/C MAINS BEING NEMA 3R WHICH |
| | IS BEING *ASSUMED* AS BEING OUTSIDE AND SHOWS PANEL *A* |
| | AS BEING NEMA 1 WHICH IS AN INDOOR RATED PIECE OF |
| | EQUIPMENT. THIS WOULD LEND TO THE FACT MAINS ARE NOT |
| | GROUPED AS NEEDED. |
| | PLEASE ALSO SEE POWER PLANS DO NOT SHOW LOCATIONS. |
| | 240.24, 110.26, 230.72 ETC |
| | FBC ADMIN SECTION 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SEE RISER SHOWS MAIN ON PANEL *A* AS |
| | 225AMPS, YET THE PANEL SCHEDULE ONLY SHOWS 200AMPS MAIN |
| | CIRCUIT BREAKER. |
| | PLEASE ALSO SEE THE SERVICE ENTRANCE CONDUCTORS FOR |
| | THIS SAME PANEL IS NOTED AS FEEDERS WHICH CAN NOTBE. |
| | PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ON PANEL *A* |
| | SCHEDULE SHOWS 3/0 WHICH ARE ONLY RATED FOR 200AMPS PER |
| | 310.16, 110.14, 240.4 AND THE RISER SHOWS 4/0. |
| | PLEASE KNOW IF THE MAIN IS GOING TO BE 225AMPS, THE 4/0 |
| | CONDUCTOR ARE RATED. |
| | PLEASE COORDINATE ALL OF THE ABOVE. |
| | 240.4, 230.70, 310.16 ETC |
| | FBC 106.3.5.1.2, 106.1.2 ADMIN SECTION. |
| | |
| | 10) NOTE: PLEASE SEE ALL CONDUITS TAPPED FROM THE |
| | GUTTER INDICATING AN EQUIPMENT GROUNDING CONDUCTOR |
| | BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| | PERMITTED. |
| | PLEASE SEE 250.6, 250.24 AS THIS WOULD CREATE |
| | OBJECTIONABLE CURRENTS. |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION WILL CHANGE, REVIEW |
| | FOR ALL ITEMS CAN NOT BE DONE AT THIS TIME. |
| | CHANGES MAY GENERATE NEW COMMENTS. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |