| 2008-01-26 19:18:02 | BUILDING PLAN REVIEW |
| | PERMIT: 08010387 |
| | ADD: 4700 BROADWAY |
| | CONT: HALLMARK & SONS |
| | TEL: (561)644-3498 |
| | JAN.26,2008 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. NOTE ONLY ONE SET OF PLANS ARE IN |
| | THE PACKAGE! |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS, SHEET A-2 IS |
| | MISSING THE SUPPLEMENTS . |
| | |
| | 2) SHEET A-2CODE SUMMARY PLEAE CORRECTTHE FOLLOWING |
| | INFORMATION OR MISSING INFORMATION.110.2* W. P. B. |
| | ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. PLANS INDICATE OCCUPANCY CLASS |
| | FOR MERCANTILE AS "B" PLEASE CORRECT. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6, |
| | TABLE 601. THE BUILDING CLASIFICATION IS FROM THE 2001 |
| | FBC PLEASE UPDATE. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | . |
| | 3)PLEASE PROVIDE SQ FT AREA FOR MERCANTILE AREA AS |
| | WELL AS THE WAREHOUSE TO SEE IF WAREHOUSE MEETS THE |
| | REQUIREMENTS OF A ACCESSORY USE AREA(302.3) NOT |
| | REQUIRING A FIRE RATED WALL. PLEASE PORVIDE |
| | CALCULATIONS. SHEETA-5 HAS A DETAIL# 4OF A 1 HR RATED |
| | WALL BUT THE FLOOR PLAN DOES NOT INDICATE WALL |
| | RATINGS? |
| | |
| | 4) THE PERMIT PACKAGE SET OF DOCUMENTS ARE MORE OF A |
| | SHELL PERMIT THAN AN AN INTERIOR AND EXTERIOR |
| | RENOVATION PERMIT. SHEET A-2 DOES NOT PROVIDE ANY |
| | INTERIOR AISLES , CASE WORK OR REFRIGARATED UNITS, |
| | ADDITIONAL INFORMATION WILL BE REQUIRED FOR THE |
| | INTERIOR? SECTION 803.1, TABLE 803.5. |
| | |
| | 5) THE PLANS INDICATE THIS IS TO BE A MERCANTILE TYPE |
| | BUSINESS BUT THERE IS NO INFORMATION ON THE INTERIOR TO |
| | INDICATE COMPLIANCE WITH 11-7, PLANS ARE NOT COMPLETE. |
| | |
| | 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) HOLLOW METAL EXTERIOR DOORS |
| | B)STOREFRONT WINDOWS- MISSING FLORIDA COVERSHEET, |
| | MISSING MIAMI-DADE COVERSHEET AND SHEET E-2 |
| | C)GLAZED EXTERIOR DOOR- MISSING FLORIDA COVERSHEET |
| | D) ROOFING REPORT DID NOT HIGHLIGHT WHICH SUB-SYSTEM |
| | THAT WILL BE INSTALLED, NOTE PRESSURES ,ANDLIMITAION |
| | EITHER 7 OR 9. |
| | E) HURRICANE RAFTER STRAPS- A-3 ANCHORING EQUIPMENT TO |
| | ROOF |
| | |
| | 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) SHEET E-1 INDICATES THE USE OF LIGHT POLES SUBMIT |
| | CALCULATIONS FOR POLES AND FIXTURES FOR 140 WIND SPEED. |
| | 1609. |
| | |
| | NOTE!!! A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, |
| | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |