| Plan Review Notes For Permit 08010376 |
| Permit Number |
08010376 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-05-01 11:35:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) PLANS PAGE E-1.0 SHOWS ONE NEW SUPPLY AND TWO NEW | | | RETURN AIR GRILL. AS REQUESTED IN LAST REVIEW1-28-08 | | | NOTE #1. PLEASE SHOW ON PLAN ALL NEW GRILL SIZES, DUCT | | | (FLEX) SIZES AND CFM'S AT NEW SUPPLY AIR GRILLS. SEE | | | 2004 FBC 106.3.5. | | | | | | 2) AS REQUESTED IN LAST REVIEW 1-28-08 NOTE #3. PLEASE | | | ADD OUTSIDE AIR CALCULATIONS TO PLANS AND PROVIDE | | | OUTSIDE AIR TO SPACE, SEE 2004 FBC/M 401.2. | | | | | | 3) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR | | | TIMES THE FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|