| 2008-04-28 17:02:11 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | ** AS NOTED ON PREVIOUS REVIEW THERE MAY CERTAINLY BE |
| | NEW COMMENTS ONCE ALL INFORMATION IS SUBMITTED FOR |
| | REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE NO LIGHTING CONTROLS IN COMPLIANCE |
| | WITH FBC 13-415.1.ABC.1.1, .1.2 AND.1.3. |
| | PLEASE KNOW THIS BUILDING IS OVER 5K SQ FT AND IS |
| | REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS FOR ALL |
| | LIGHTING. |
| | AS NO SYSTEM OR LIGHTING CONTROLS DEVICES ARE SHOWN AT |
| | THIS TIME IN COMPLIANCE WITH THE FLORIDA BUILDING CODE |
| | CHAPTER 13 SECTIONS AS GIVEN ABOVE ARE NOT SHOWN NO |
| | REVIEW OF THESE ITEMS CAN BE DONE AT THIS TIME. |
| | |
| | 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS AS REQUESTED ON PREVIOUS REVIEW IN |
| | COMPLIANCE WITH FBC 13-415.2.ABC.1.1, .1.2. |
| | PLEASE KNOW ALSO AS MENTIONED ABOVE MINIMUM CODE |
| | COMPLIANCE IS NOT YET SHOWN. |
| | |
| | 3) NOTE: PLEASE SEE NOW PLANS SHOW CIRCUITING ETC |
| | HOWEVER CIRCUITS ON PANEL SCHEDULE NEED TO BE SPECIFIC |
| | TO AREAS AND ITEMS IN WHICH THEY FEED. |
| | 408.4 |
| | |
| | 4) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER |
| | 210.62 |
| | |
| | 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER NEC |
| | 220. |
| | PLEASE SEE LOADS FOR SHOW WINDOWS PER 220.43A |
| | PLEASE SEE LOADS FOR TRACK LIGHTING NEED TO BE SHOWN |
| | PER 220.43B. |
| | PLEASE SEE NO CONTINUOUS LOADS SHOWN AT 125% PER 215.3, |
| | 230.42 ETC. |
| | |
| | 6) NOTE: PLEASE SEE THE OWNER INFORMATION ON THE PERMIT |
| | APPLICATION NEEDS TO BE UPDATED AS THE OWNER IS NOT |
| | JOHNNY'S DREAM INC. THIS IS THE TENANTS NAME AND OWNER |
| | OF SAID BUILDING IS ATTACHED TO ELECTRICAL NOTES FOR |
| | INFORMATION. PLEASE ADJUST. |
| | |
| | 7) NOTE: PLEASE INDICATE THE ELECTRICAL AND RELEVANT |
| | CODE ON ELECTRICAL SHEETS AS PREVIOUSLY NOTED. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-70 |
| | |
| | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | PLANS MAY BE RETAINED BY THIS OFFICE. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |