| Plan Review Notes For Permit 08010351 |
| Permit Number |
08010351 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-28 16:06:37 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.SUBMIT AN EXISTING FLOOR PLAN SO THAT COMPARITIVES | | | MAY BE EXAMINED AGAINST PROPOSED FLOOR PLAN. | | | | | | 3.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF | | | BUILDING WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF | | | SO, THIS SHALL BE PERMITTED ONLY WHERE REQUIRED MEANS | | | OF EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN | | | PLACE AND CONTINUOUSLY MAINTAINED. | | | | | | 4.PLEASE INDICATE IF THE BUILDING HAS A FIRE ALARM | | | SYSTEM.IF PROJECT SCOPE OF WORK HAS CAUSE FOR THE | | | FIRE ALARM SYSTEM TO BE REMODELED, SEPARATE PLANS AND | | | PERMIT WILL BE REQUIRED. | | | | | | 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 6.SPECIFY THE NEW INTERIOR WALL FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 7.ON SHEET A-1 IN THE CAPTION FOR DOORS REGARDING | | | EGRESS, ACCESSIBILITY, AND OPERATION, REFERENCE SHALL | | | BE MADE TO THE 2003 EDITION OF NFPA. | | | | | | 8. HOW WILL THE TENANT SPACES BE ADDRESSED AS SUCH TO | | | DISTINGUISH ONE FROM THE OTHER? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | INDICATING WHERE ON THE PLAN EACH ITEM HAS BEEN | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|