| 2008-01-18 16:15:53 | |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING RELEVANT CODES SHALL |
| | BE STATED ON PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (WHERE APPLICABLE) |
| | |
| | ** PLEASE SEE PLANS NOTE 2000 LS-101 AND 2001 FBC IN |
| | SOME LOCATIONS. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE |
| | CALCULATIONS FOR EXISTING AND NEW PROPOSED. MAY NOT ADD |
| | NEW LIGHTING UNLESS FALLING UNDER THE MAXIMUM |
| | ALLOWANCES PER 13-415.2. |
| | |
| | 3) NOTE: PLEASE PROVIDE INFORMATION ON WEST EXISTING |
| | SPACE WHICH IS PART OF THE EXISTING STORE. HOW WILL THE |
| | EXISTING LIGHTING BE FED? HOW WILL THE MINIMUM SPACE |
| | LIGHTING MEET LS CODE WITHOUT ANYELECTRICAL BEING |
| | SHOWN TO THIS AREA. |
| | PLEASE KNOW THE SPACE WILL REQUIRE MINIMUM LIGHTING FOR |
| | LIFE SAFETY 101 7.8 AND 7.9 |
| | |
| | 4) NOTE: PLEASE SHOW WHAT CIRCUITS ON PANEL SCHEDULE |
| | ARE EXISTING AND WHICH ONES ARE NEW. |
| | 408.4, |
| | FBC 106.1.2, 103.5.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 5) NOTE: PLEASE INDICATE ANY FIRE ALARMS HORNS AND |
| | STROBES IN COMPLIANCE WITH FBC 11-4.28.1,.2 AND .3(4). |
| | (WHERE APPLICABLE IF BUILDING CONTAINS FA PANEL/SYSTEM) |
| | ALREADY SHOWN AS FIRE SPRINKLED. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |