| 2008-01-23 12:53:42 | |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | ** PLANS SHOW THE 2002 NFPA-70 |
| | |
| | 2) NOTE: PLEASE SEE PLANS DO NOT CONTAIN ANY |
| | INFORMATION, SIGNATURE, PRINTED NAME FOR ANY DESIGN |
| | PROFESSIONAL AS REQUIRED PER FAC, FBC ADMIN SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH 106.5, 106.1.2. |
| | FS 481.229, 471.003 OR 468. |
| | PLEASE SEE EXCEPTIONS IN 481.229 AND 471.003. |
| | |
| | 3) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE SMOKE |
| | DETECTION DEVICES NOTED ON PLANS ARE SHOWN AND NOTED A |
| | *SMOKE DETECTORS*. SMOKE DETECTORS ONLY DETECT AND DO |
| | NOT SOUND AND ALARM. PLEASE SEE DEFINITION OF SMOKE |
| | ALARMS AS STATED IN NFPA-72 AND FBC R313. |
| | PLANS MENTIONS SD, WHERE THIS SEEMS TO BE THESE SHOULD |
| | BE SA. |
| | PLEASE ADJUST. |
| | PLEASE SEE NFPA-72 11.5.1.1 FOR LOCATIONS REQUIRED. |
| | PLEASE SEE MISSING SA OUTSIDE MASTER SLEEPING ROOM. |
| | |
| | 4) NOTE: PLEASE SEE THE LIGHTING CONTROL FOR EGRESS |
| | FROM THE MASTER BEDROOM HALLWAY NEEDS TO BE LOCATED |
| | INSIDE THAT HALLWAY BEFORE EGRESS OUT OF THE REAR PATIO |
| | DOOR. |
| | PLEASE RELOCATE SWITCH. |
| | 210.70, LS 101 7.8 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52 ON |
| | MASTER BEDROOM WALL WHICH IS GREATER THAN 2FT. |
| | |
| | 6) NOTE: PLEASE SEE MINIMUM OVER CURRENT PROTECTION FOR |
| | THE 10KE HEAT-STRIP SHALL BE SIZED AT A MINIMUM OF 125% |
| | PER 424.3B. |
| | |
| | 7) NOTE: PLEASE LIST ALL ITEMS ON PANEL SCHEDULE WHICH |
| | ARE NEW OR ALREADY EXISTS. |
| | PLEASE SEE SOME ITEMS ARE LABELED AS NEW HOWEVER NOT |
| | ALL. |
| | FOR EXAMPLE: WATER HEATER, WASHER, DRYER ETC. |
| | THIS ITEMS ARE SHOWN AS NEW ON PLANS. |
| | 408.4. |
| | FBC 106.3.5.4 |
| | |
| | 8) NOTE: PLEASE SEE ELECTRICAL PLANS DOES INDICATE A |
| | NEW A/C WALL UNIT HOWEVER THERE IS NO DEDICATE CIRCUIT |
| | OR LOAD SHOWN ON PANEL SCHEDULE. |
| | 240.4, 408.4, 310.16, 220 ETC |
| | PLEASE BE SURE TO SEE 210.12 FOR REQUIRED AFCI |
| | PROTECTION OF THIS UNIT. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |