| 2008-01-31 17:00:33 | RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW |
| | UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. IT WAS UPDATED TO $6,274AS REQUIRED BY |
| | SEC. 108.3 CITY AMENDMENTSTO FBC 2004.OWES $77.43 |
| | FOR UPDATED PERMIT VALUATION AND RADON FEES. |
| | |
| | 2-PLEASE COORDINATEWITH ZONING TO SEE IF PROPOSED |
| | PORCH MEETS THE REQUIRED SETBACKS. |
| | |
| | 3- PROVIDE COMPLETE SET OF CONSTRUCTION DRAWINGS |
| | SHOWING ALL THE DESIGN CRITERIA REQUIRED BY SEC. R301.1 |
| | OF 2004 FLORIDA RESIDENTIAL CODE.NEED TO SPECIFY ALL |
| | LIVE LOADS, DEAD LOADS, WIND LOADS AND UPLIFT LOADS. |
| | PROVIDECOMPLETE FOUNDATION PLAN,FLOOR PLAN AND ROOF |
| | FRAMING PLAN. SPECIFY ALLSTRUCTURAL MEMBERS SIZES AND |
| | CONNECTIONS. |
| | |
| | 4- PERSON RESPONSIBLE FOR THE DESIGNNEEDS TO PROVIDE |
| | NAME AND SIGNATURE IN ALL DRAWINGS.IF ARCHITECT OR |
| | ENGINEER IS RESPONSIBLE FOR THE DESIGN, THENSIGN AND |
| | SEAL DRAWINGS AS REQUIRED BY CHAPTER 481 AND 471 |
| | RESPECTIVELY. SEC. 106.1 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- SPECIFY ROOF PITCH TO VERIFY COMPLIANCE WITH SLOPE |
| | REQUIRED FOR ROOF SHINGLES SEC. R905.2.2 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE |
| | FOR MINIMUMTYPE AND SPACING OF NAIL REQUIRED FOR ROOF |
| | SHEATHING INSTALLATION. INCLUDING ON ROOF ZONE 3. |
| | |
| | 7- SPECIFY ATTACHMENT OF PROPOSED PORCH TO EXISTING |
| | STRUCTURE TO VERIFY COMPLIANCE WITHTHE CALCULATED |
| | WIND LOADS AS REQUIRED BY SEC. R301.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | NOTE:TAKE INTO CONSIDERATION THAT THIS IS A MOBILE |
| | HOME AND PROPOSED PORCH WILL AFFECT THE STRUCTURAL |
| | STABILITY OF THE MAIN HOUSE. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL(2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES. |
| | |
| | B) ALL STRUCTURALCONNECTORS (SIMPSON OR USP) |
| | SPECIFIED ON PLANS AND DETAILS. |
| | |
| | 9- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| | APPROVED IN WRITING(NOT SIGNING AND SEALING)BY THE |
| | DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |