| Plan Review Notes For Permit 08010322 |
| Permit Number |
08010322 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-02-29 17:14:50 | ** REDLINED PLANS ** | | | | | | 1) NOTE: MISSING RECEPTACLE SPACING ALONG KITCHEN | | | COUNTER SPACE PER 210.52C1 | | | | | | 2) NOTE: MISSING GFI PROTECTION ON ALL RECEPTACLES | | | SERVING KITCHEN, BAR AND ISLAND COUNTER SPACES PER | | | 210.8A6. | | | | | | 3) NOTE: SMOKE DETECTION DEVICES SHOULD BE SMOKE ALARMS | | | WHICH DETECT AND SOUND. NFPA-72 | | | | | | 4) BREAKER FOR DISHWASHER AND DISPOSAL TO MEET 210.4B | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|