2008-01-22 10:00:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE
 RESUBMITTED PLANS FOR THE PROPOSED SHOWER.
  
 A} PER FBC PLUMBING SCTION *417.4.1 WALL AREA. THE
 WALL AREA ABOVE BUILT-IN TUBS WITH INSTALLED SHOWER
 HEADS AND IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED
 OF SMOOTH, NONCORROSIVE AND NONABSORBENT WATERPROOF
 MATERIALS TO A HEIGHT NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) WHERE MEASURED FROM THE COMPARTMENT FLOOR AT
 THE DRAIN. SUCH WALLS SHALL FORM A WATER-TIGHT JOINT
 WITH EACH OTHER AND WITH EITHER THE TUB, RECEPTOR OR
 SHOWER FLOOR.
  
 B} PER FBC PLUMBING SECTION *417.5 SHOWER FLOORS OR
 RECEPTORS.
 FLOOR SURFACES SHALL BE CONSTRUCTED OF IMPERVIOUS,
 NONCORROSIVE, NONABSORBENT AND WATERPROOF MATERIALS.
  
 C} PER FBC PLUMBING SECTION *424.3 SHOWER VALVES.
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016 OR CSA B125. SHOWER AND
 TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION
 SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM
 SETTING OF THE VALVE TO 120?F (49?C), WHICH SHALL BE
 FIELD ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 D} PER FBC BUILDING SECTION *2406.3 (5) HAZARDOUS
 LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS:
 5.GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS,
 WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS.
 GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING
 THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A
 STANDING SURFACE.
 **PLEASE INDICATE THAT THE SHOWER DOORS ARE COMPLIANT
 IN THE RESUBMITTAL.
  
 **PLANS ARE INDICATING GAS TO A PROPOSED NEW KITCHEN
 ISLAND RANGE/OVEN. THE FOLLOWING INFORMATION WILL BE
 REQUIRED ON A SEPERATE GAS PERMIT APPLICATION FOR THE
 PROPOSED WORK. A LICENSED GAS OR PLUMBING CONTRACTOR
 SHALL SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS
 INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION.
  
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B}SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C} TYPE OF GAS, (LP OR NATURAL)
  
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F} SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G} INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H} 404.11 PIPING UNDERGROUND BENEATH BUILDINGS. PIPING
 INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED
 EXCEPT WHERE THE PIPING IS ENCASED IN A CONDUIT OF
 WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE DESIGNED TO
 WITHSTAND THE SUPERIMPOSED LOADS. SUCH CONDUIT SHALL
 EXTEND INTO AN OCCUPIABLE PORTION OF THE BUILDING AND,
 AT THE POINT WHERE THE CONDUIT TERMINATES IN THE
 BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE GAS
 PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE ENTRANCE
 OF ANY GAS LEAKAGE. WHERE THE END SEALING IS CAPABLE OF
 WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE, THE
 CONDUIT SHALL BE DESIGNED FOR THE SAME PRESSURE AS THE
 PIPE. SUCH CONDUIT SHALL EXTEND NOT LESS THAN 4 INCHES
 (102 MM) OUTSIDE THE BUILDING, SHALL BE VENTED ABOVE
 GRADE TO THE OUTDOORS AND SHALL BE INSTALLED SO AS TO
 PREVENT THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT
 SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE WITH
 SECTION 404.8 . (DETAIL REQUIRED)
  
 I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J} CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K} CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  