Plan Review Notes
Plan Review Notes For Permit 08010322
Permit Number 08010322
Review Stop G
Sequence Number 1
Notes
Date Text
2008-02-25 17:00:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME, NOTE: 1ST REVIEW FOR GAS WAS DONE
 UNDER PLUMBING REVIEW:
  
 THE FOLLOWING COMMENTS ARE LETTERED TO CORRESPOND WITH
 THE PREVIOUS REVIEW COMMENTS DONE UNDER THE PLUMBING
 REVIEW AS WELL AS THE DESIGNER'S RESPONSES FOR THE
 PURPOSE OF CONTINUITY. **NOTE: THERE WERE NO COMMENT
 RESPONSES FROM THE DESIGNER.
  
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NO COMMENT RESPONSE, THE RESUBMITTED PLANS DO HAVE A
 GAS ISOMETRIC RISER DIAGRAM, HOWEVER THE EXISTING
 NATURAL GAS SYSTEM TO THE POOL HEATER AND BBQ ARE NOT
 BEING INDICATED. PLEASE REFERENCE THE PERMIT
 INFORMATION INDICATING EXISTING NATURAL GAS TO THESE
 APPLIANCES.
  
 B} **OK** COMMENT ADDRESSED.
  
 C} **OK** COMMENT ADDRESSED.
  
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **NO COMMENT RESPONSE, THE RESUBMITTED PLANS ARE
 INDICATING A BTU LOAD FOR THE NEW GAS RANGE AS BEING
 15,000 BTU'S. PER THE SUBMITTAL OF THE APPLIANCE THE
 15,000 BTU LOAD FOR THE NEW GAS RANGE IS FOR ONE BURNER
 ONLY. PLEASE KNOW THAT THERE ARE THREE DIFFERENT MODELS
 IN THE SUBMITTAL PACKAGE AND ALL THREE WILL HAVE A
 DIFFERENT BTU LOAD. PLEASE CLEARLY INDICATE THE MODEL
 BEING USED AND CORRECTLY CALCULATE THE BTU LOAD OF THE
 MODEL. ALSO THE EXISTING BTU LOAD FOR THE POOL HEATER
 AND BBQ NEED TO BE ON THE RESUBMITTED PLANS.
  
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NO COMMENT RESPONSE, THE EXISTING NATURAL GAS SYSTEM
 FROM THE METER TO THE POOL HEATER AND BBQ NEEDS TO BE
 INCLUDED AS WELL AS THE GAS TO THE PROPOSED NEW RANGE.
 A GAS PLAN REVIEW CAN NOT BE DONE WITHOUT THE LONGEST
 LENGTH OF THE SYSTEM BEING KNOWN.
  
 F} **OK** N/A.
  
 G} **OK** COMMENT ADDRESSED.
  
 H} 404.11 PIPING UNDERGROUND BENEATH BUILDINGS. PIPING
 INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED
 EXCEPT WHERE THE PIPING IS ENCASED IN A CONDUIT OF
 WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE DESIGNED TO
 WITHSTAND THE SUPERIMPOSED LOADS. SUCH CONDUIT SHALL
 EXTEND INTO AN OCCUPIABLE PORTION OF THE BUILDING AND,
 AT THE POINT WHERE THE CONDUIT TERMINATES IN THE
 BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE GAS
 PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE ENTRANCE
 OF ANY GAS LEAKAGE. WHERE THE END SEALING IS CAPABLE OF
 WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE, THE
 CONDUIT SHALL BE DESIGNED FOR THE SAME PRESSURE AS THE
 PIPE. SUCH CONDUIT SHALL EXTEND NOT LESS THAN 4 INCHES
 (102 MM) OUTSIDE THE BUILDING, SHALL BE VENTED ABOVE
 GRADE TO THE OUTDOORS AND SHALL BE INSTALLED SO AS TO
 PREVENT THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT
 SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE WITH
 SECTION 404.8 . (DETAIL REQUIRED)
 **NO COMMENT RESPONSE OR DETAIL PROVIDED, COMMENT NOT
 ADDRESSED. PLEASE REFERENCE THE UNDERGROUND GAS PIPE
 BENEATH BUILDING DETAIL ATTACHED TO THESE COMMENTS FOR
 THE RESUBMITTAL CORRECTION.
  
 I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NO COMMENT RESPONSE, THE SUBMITTED MANUFACTURER
 SHEETS OF THE PROPOSED RANGE HAVE THREE DIFFERENT
 MODELS BEING INDICATED, PLEASE CLEARLY INDICATE THE
 MODEL BEING USED AND CLEARLY INDICATE THE CORRECT BTU
 LOAD (SEE COMMENT "D" ABOUT CORRECT BTU'S FOR PROPOSED
 RANGE).
  
 J} **OK** N/A.
  
 K} **OK** N/A.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  