| 2008-02-25 17:00:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED 2ND TIME, NOTE: 1ST REVIEW FOR GAS WAS DONE |
| | UNDER PLUMBING REVIEW: |
| | |
| | THE FOLLOWING COMMENTS ARE LETTERED TO CORRESPOND WITH |
| | THE PREVIOUS REVIEW COMMENTS DONE UNDER THE PLUMBING |
| | REVIEW AS WELL AS THE DESIGNER'S RESPONSES FOR THE |
| | PURPOSE OF CONTINUITY. **NOTE: THERE WERE NO COMMENT |
| | RESPONSES FROM THE DESIGNER. |
| | |
| | A} SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NO COMMENT RESPONSE, THE RESUBMITTED PLANS DO HAVE A |
| | GAS ISOMETRIC RISER DIAGRAM, HOWEVER THE EXISTING |
| | NATURAL GAS SYSTEM TO THE POOL HEATER AND BBQ ARE NOT |
| | BEING INDICATED. PLEASE REFERENCE THE PERMIT |
| | INFORMATION INDICATING EXISTING NATURAL GAS TO THESE |
| | APPLIANCES. |
| | |
| | B} **OK** COMMENT ADDRESSED. |
| | |
| | C} **OK** COMMENT ADDRESSED. |
| | |
| | D} BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | **NO COMMENT RESPONSE, THE RESUBMITTED PLANS ARE |
| | INDICATING A BTU LOAD FOR THE NEW GAS RANGE AS BEING |
| | 15,000 BTU'S. PER THE SUBMITTAL OF THE APPLIANCE THE |
| | 15,000 BTU LOAD FOR THE NEW GAS RANGE IS FOR ONE BURNER |
| | ONLY. PLEASE KNOW THAT THERE ARE THREE DIFFERENT MODELS |
| | IN THE SUBMITTAL PACKAGE AND ALL THREE WILL HAVE A |
| | DIFFERENT BTU LOAD. PLEASE CLEARLY INDICATE THE MODEL |
| | BEING USED AND CORRECTLY CALCULATE THE BTU LOAD OF THE |
| | MODEL. ALSO THE EXISTING BTU LOAD FOR THE POOL HEATER |
| | AND BBQ NEED TO BE ON THE RESUBMITTED PLANS. |
| | |
| | E} SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **NO COMMENT RESPONSE, THE EXISTING NATURAL GAS SYSTEM |
| | FROM THE METER TO THE POOL HEATER AND BBQ NEEDS TO BE |
| | INCLUDED AS WELL AS THE GAS TO THE PROPOSED NEW RANGE. |
| | A GAS PLAN REVIEW CAN NOT BE DONE WITHOUT THE LONGEST |
| | LENGTH OF THE SYSTEM BEING KNOWN. |
| | |
| | F} **OK** N/A. |
| | |
| | G} **OK** COMMENT ADDRESSED. |
| | |
| | H} 404.11 PIPING UNDERGROUND BENEATH BUILDINGS. PIPING |
| | INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED |
| | EXCEPT WHERE THE PIPING IS ENCASED IN A CONDUIT OF |
| | WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE DESIGNED TO |
| | WITHSTAND THE SUPERIMPOSED LOADS. SUCH CONDUIT SHALL |
| | EXTEND INTO AN OCCUPIABLE PORTION OF THE BUILDING AND, |
| | AT THE POINT WHERE THE CONDUIT TERMINATES IN THE |
| | BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE GAS |
| | PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE ENTRANCE |
| | OF ANY GAS LEAKAGE. WHERE THE END SEALING IS CAPABLE OF |
| | WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE, THE |
| | CONDUIT SHALL BE DESIGNED FOR THE SAME PRESSURE AS THE |
| | PIPE. SUCH CONDUIT SHALL EXTEND NOT LESS THAN 4 INCHES |
| | (102 MM) OUTSIDE THE BUILDING, SHALL BE VENTED ABOVE |
| | GRADE TO THE OUTDOORS AND SHALL BE INSTALLED SO AS TO |
| | PREVENT THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT |
| | SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE WITH |
| | SECTION 404.8 . (DETAIL REQUIRED) |
| | **NO COMMENT RESPONSE OR DETAIL PROVIDED, COMMENT NOT |
| | ADDRESSED. PLEASE REFERENCE THE UNDERGROUND GAS PIPE |
| | BENEATH BUILDING DETAIL ATTACHED TO THESE COMMENTS FOR |
| | THE RESUBMITTAL CORRECTION. |
| | |
| | I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **NO COMMENT RESPONSE, THE SUBMITTED MANUFACTURER |
| | SHEETS OF THE PROPOSED RANGE HAVE THREE DIFFERENT |
| | MODELS BEING INDICATED, PLEASE CLEARLY INDICATE THE |
| | MODEL BEING USED AND CLEARLY INDICATE THE CORRECT BTU |
| | LOAD (SEE COMMENT "D" ABOUT CORRECT BTU'S FOR PROPOSED |
| | RANGE). |
| | |
| | J} **OK** N/A. |
| | |
| | K} **OK** N/A. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |