Plan Review Notes
Plan Review Notes For Permit 08010322
Permit Number 08010322
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-18 14:31:57 
  
 ** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
  
 ** PLEASE ALSO SEE PLANS CONTAINS NOTES FOR PALM BEACH
 COUNTY HOWEVER SCOPE OF WORK AS APPLIED IS LOCATED IN
 THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE FBC R313 AND SHOW ALL NEW OR
 EXISTING LOCATIONS FOR SMOKE ALARMS MEETING THE CURRENT
 NFPA-72 11.5.1.1.1.
  
 3) NOTE: PLEASE SUBMIT PANEL SCHEDULE SHOWING THE SIZE
 OF THE EXISTING PANEL WITH NEW LOADS ALONG WITH
 EXISTING LOADS.
 PLANS INDICATE 200 AMPS, HOWEVER NEED TO SHOW THE
 ENTIRE EXISTING LOAD ON THE 200AMP SERVICE AS NOTED.
 PLANS INDICATE OTHER NEW DEDICATE CIRCUITS YET THE
 ABBREVIATED CALCULATIONS DO NOT INCLUDE THESE OTHER NEW
 LOADS. FOR EXAMPLE: PLEASE SEE OVEN> ETC
  
 4) NOTE: PLEASE SUBMIT AND INDICATE ON PANEL SCHEDULE
 THE MINIMUM CIRCUITS FOR NEW OR EXISTING SMALL
 APPLIANCE CIRCUITS PER 210.52B1, 210.11C1, 220.53.
 PLEASE SEE 220.83 FOR EXISTING SERVICE LOADS.
 PLEASE INDICATE THE BRANCH CIRCUIT SIZES OF CONDUCTORS
 AND OVER CURRENT PROTECTION.
 408.4, 240.4, 310.16 ETC
 FBC 106.3.5.4, 106.1.2 FOR ADDITIONAL INFORMATION
 NEEDED.
  
 5) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI/GFI PROTECTED.
  
 6) NOTE: PLEASE SEE 210.52C1 FOR MISSING COUNTER SPACE
 RECEPTACLES REQUIRED.
  
 7) NOTE: PLEASE PLACE TYPE OF FIXTURES FOR RECESSED
 LIGHTING TO MEET FBC 13-606.1.ABC.1.2.4
  
  
 ** PLEASE KNOW AS SOME INFORMATION IS NOT YET SUBMITTED
 FULL REVIEW FOR CODE COMPLIANCE CAN BE DONE AT THIS
 TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  