| 2008-01-18 14:31:57 | |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| | ON PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE ALSO SEE PLANS CONTAINS NOTES FOR PALM BEACH |
| | COUNTY HOWEVER SCOPE OF WORK AS APPLIED IS LOCATED IN |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SEE FBC R313 AND SHOW ALL NEW OR |
| | EXISTING LOCATIONS FOR SMOKE ALARMS MEETING THE CURRENT |
| | NFPA-72 11.5.1.1.1. |
| | |
| | 3) NOTE: PLEASE SUBMIT PANEL SCHEDULE SHOWING THE SIZE |
| | OF THE EXISTING PANEL WITH NEW LOADS ALONG WITH |
| | EXISTING LOADS. |
| | PLANS INDICATE 200 AMPS, HOWEVER NEED TO SHOW THE |
| | ENTIRE EXISTING LOAD ON THE 200AMP SERVICE AS NOTED. |
| | PLANS INDICATE OTHER NEW DEDICATE CIRCUITS YET THE |
| | ABBREVIATED CALCULATIONS DO NOT INCLUDE THESE OTHER NEW |
| | LOADS. FOR EXAMPLE: PLEASE SEE OVEN> ETC |
| | |
| | 4) NOTE: PLEASE SUBMIT AND INDICATE ON PANEL SCHEDULE |
| | THE MINIMUM CIRCUITS FOR NEW OR EXISTING SMALL |
| | APPLIANCE CIRCUITS PER 210.52B1, 210.11C1, 220.53. |
| | PLEASE SEE 220.83 FOR EXISTING SERVICE LOADS. |
| | PLEASE INDICATE THE BRANCH CIRCUIT SIZES OF CONDUCTORS |
| | AND OVER CURRENT PROTECTION. |
| | 408.4, 240.4, 310.16 ETC |
| | FBC 106.3.5.4, 106.1.2 FOR ADDITIONAL INFORMATION |
| | NEEDED. |
| | |
| | 5) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| | KITCHEN COUNTER SPACE SHALL BE GFI/GFI PROTECTED. |
| | |
| | 6) NOTE: PLEASE SEE 210.52C1 FOR MISSING COUNTER SPACE |
| | RECEPTACLES REQUIRED. |
| | |
| | 7) NOTE: PLEASE PLACE TYPE OF FIXTURES FOR RECESSED |
| | LIGHTING TO MEET FBC 13-606.1.ABC.1.2.4 |
| | |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION IS NOT YET SUBMITTED |
| | FULL REVIEW FOR CODE COMPLIANCE CAN BE DONE AT THIS |
| | TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |