| 2008-02-12 16:52:15 | *****DENIED***** |
| | |
| | |
| | 1. THE CORRECT SUITE NUMBER SHALL BE LISTED AS PART OF |
| | THE PROJECT SITE ADDRESS. PLEASE SEE THAT SUITE 100 AND |
| | SUITE 1000 ARE SHOWN ON THE SUBMITTED PLAN SHEETS AND |
| | STRUCTURAL CALCULATIONS DOCUMENTS. PLEASE |
| | RECTIFY. |
| | |
| | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 4. PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED |
| | DURING THE SCOPE OF WORK. IF SO, MEANS OF EGRESS AND |
| | AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN |
| | PLACE AND CONTINUOUSLY MAINTAINED. |
| | |
| | 5. PLEASE LIST THE FOLLOWING FOR THE BUILDING: |
| | OCCUPANCY TYPE, OCCUPANT LOAD, FIRE ALARM AND/OR FIRE |
| | SPRINKLER DEVICES, AND ANY OTHER PERTINENT |
| | INFORMATION. |
| | |
| | 6. PLEASE PROVIDE A CLEAR REPRENSENTATION OF THE |
| | MEZZANINE IN RELATION TO THE FLOOR PLAN INCLUDING EXIT |
| | LIGHTS/DOORS, EMERGENCY LIGHTS, ETC. |
| | |
| | 7. HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE |
| | SPRINKLER AND FIRE ALARM DEVICES. |
| | |
| | 8. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |