| Date |
Text |
| 2008-04-24 13:55:22 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME OF THE EXACT SAME NOTES ARE IN NEED |
| | OF ADDRESSING. PLEASE ALSO SEE SOME NEW NOTES DUE TO |
| | THIS BEING THE SECOND REVIEW AND SOME PROJECT DOCUMENTS |
| | NOW SUBMITTED HAVE CHANGED. |
| | |
| | 1) NOTE:PLEASE SEE THE VERSION OF ENERGY CALCULATIONS |
| | SUBMITTED IS NOT ADOPTED BY THE FBC. PLEASE SEE |
| | 13-400.3.B, 13-400.A AS THIS VERSION SHALL BE 2.5. |
| | THE ENERGY GAUGE WEBSITE STATES THE ENERGY GAUGE SUMMIT |
| | VERSIONS 3.0-3.14 ARE ACCEPTABLE; HOWEVER PLEASE ALSO |
| | READ THE REMAINDER OF THE SENTENCE AS IT STATES THESE |
| | ARE INCORPORATED INTO THE VERSION 2.5. IN OTHER WORDS, |
| | THE VERSION WHICH IS SHOWN ON THE TOP OF THE PAGE |
| | SHOULD READ 2.5. THIS OFFICE HAS SPOKEN TO THE |
| | DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA BUILDING |
| | SPECIFICALLY ABOUT THIS AND THEIR RESPONSE IS THE CODE |
| | CLEARLY STATES VERSION 2.5. |
| | PLEASE BE SURE TO REVISE VERSION. THIS REVIEWER PLACED |
| | A CALL TO ENGINEER AND DESIGNER OF THIS PROJECT ON |
| | TUESDAY THE 22ND OF APRIL HOWEVER AS OF THIS REVIEW NO |
| | RETURN CALL HAS BEEN MADE TO THIS OFFICE. NEED TO |
| | DISCUSS THE CALCULATIONS. |
| | ** PLEASE EXPLAIN HOW METHOD *B* CAN BE USED. THIS IS |
| | NOT A WHOLE BUILDING AND DOES NOT QUALIFY AS A |
| | RENOVATION OF THE *BUILDING* BY DEFINITIONS. |
| | LIGHTING PERFORMANCE CALCULATIONS FOR LIGHTING |
| | COMPLIANCE LEVELS IS REQUIRED FOR THIS REVIEWER. PLEASE |
| | SEE ANY OTHER POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT HOW THE CALCULATIONS NEED TO BE DONE FOR |
| | MECHANICAL SYSTEMS ETC. |
| | |
| | 2) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS DETAIL NOW |
| | ADDED TO E SHEET 2 OF 3 SHOWS OCCUPANCY SENSOR(S) YET |
| | THE PLANS DO NOT SHOWN ANY OF THESE DEVICES. |
| | PLEASE ALSO SEE THIS SAME DETAIL STATES OVER RIDES |
| | DEVICES AS *OPTIONAL* WHEN IN FACT THE PLANS SHOW THESE |
| | DEVICES BEING INSTALLED. |
| | PLEASE COORDINATE SYSTEM AND ALL DEVICES REQUIRED BY |
| | CODE AND WHAT WILL BE INSTALLED PER DESIGN. |
| | 13-415.1.ABC.1.1, .2 AND .1.3. |
| | PLEASE VERIFY HOW LIGHTING PANEL WILL FEED THE CIRCUITS |
| | WHEN THE RISER SHOWS THE LIGHTING PANEL BEING FED FROM |
| | PANEL *B*. THE PLANS INDICATE THE LIGHTING CIRCUITS |
| | THROUGH PANEL *A*. |
| | PLEASE ALSO VERIFY HOW THE OUTSIDE LIGHT SHOWN ON THE |
| | SWITCH MEETS 13-415.1.ABC.1.4. THERE ARE TWO TYPES OF |
| | CONTROLS REQUIRED. BASED ON THE ELECTRICAL RISER AND |
| | INFORMATION SHOWN ON PLANS THIS DOES NOT MEET EITHER. |
| | PLEASE KNOW AN ASTRONOMICAL TIME CLOCK W/ A MINIMUM OF |
| | 10HR BACK UP FOR PROGRAMMING OR PHOTO-SENSOR IS THE TWO |
| | OPTIONS. |
| | |
| | 3) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |