Plan Review Notes
Plan Review Notes For Permit 08010276
Permit Number 08010276
Review Stop E
Sequence Number 3
Notes
Date Text
2008-04-24 13:55:22** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME OF THE EXACT SAME NOTES ARE IN NEED
 OF ADDRESSING. PLEASE ALSO SEE SOME NEW NOTES DUE TO
 THIS BEING THE SECOND REVIEW AND SOME PROJECT DOCUMENTS
 NOW SUBMITTED HAVE CHANGED.
  
 1) NOTE:PLEASE SEE THE VERSION OF ENERGY CALCULATIONS
 SUBMITTED IS NOT ADOPTED BY THE FBC. PLEASE SEE
 13-400.3.B, 13-400.A AS THIS VERSION SHALL BE 2.5.
 THE ENERGY GAUGE WEBSITE STATES THE ENERGY GAUGE SUMMIT
 VERSIONS 3.0-3.14 ARE ACCEPTABLE; HOWEVER PLEASE ALSO
 READ THE REMAINDER OF THE SENTENCE AS IT STATES THESE
 ARE INCORPORATED INTO THE VERSION 2.5. IN OTHER WORDS,
 THE VERSION WHICH IS SHOWN ON THE TOP OF THE PAGE
 SHOULD READ 2.5. THIS OFFICE HAS SPOKEN TO THE
 DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA BUILDING
 SPECIFICALLY ABOUT THIS AND THEIR RESPONSE IS THE CODE
 CLEARLY STATES VERSION 2.5.
 PLEASE BE SURE TO REVISE VERSION. THIS REVIEWER PLACED
 A CALL TO ENGINEER AND DESIGNER OF THIS PROJECT ON
 TUESDAY THE 22ND OF APRIL HOWEVER AS OF THIS REVIEW NO
 RETURN CALL HAS BEEN MADE TO THIS OFFICE. NEED TO
 DISCUSS THE CALCULATIONS.
 ** PLEASE EXPLAIN HOW METHOD *B* CAN BE USED. THIS IS
 NOT A WHOLE BUILDING AND DOES NOT QUALIFY AS A
 RENOVATION OF THE *BUILDING* BY DEFINITIONS.
 LIGHTING PERFORMANCE CALCULATIONS FOR LIGHTING
 COMPLIANCE LEVELS IS REQUIRED FOR THIS REVIEWER. PLEASE
 SEE ANY OTHER POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT HOW THE CALCULATIONS NEED TO BE DONE FOR
 MECHANICAL SYSTEMS ETC.
  
 2) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS DETAIL NOW
 ADDED TO E SHEET 2 OF 3 SHOWS OCCUPANCY SENSOR(S) YET
 THE PLANS DO NOT SHOWN ANY OF THESE DEVICES.
 PLEASE ALSO SEE THIS SAME DETAIL STATES OVER RIDES
 DEVICES AS *OPTIONAL* WHEN IN FACT THE PLANS SHOW THESE
 DEVICES BEING INSTALLED.
 PLEASE COORDINATE SYSTEM AND ALL DEVICES REQUIRED BY
 CODE AND WHAT WILL BE INSTALLED PER DESIGN.
 13-415.1.ABC.1.1, .2 AND .1.3.
 PLEASE VERIFY HOW LIGHTING PANEL WILL FEED THE CIRCUITS
 WHEN THE RISER SHOWS THE LIGHTING PANEL BEING FED FROM
 PANEL *B*. THE PLANS INDICATE THE LIGHTING CIRCUITS
 THROUGH PANEL *A*.
 PLEASE ALSO VERIFY HOW THE OUTSIDE LIGHT SHOWN ON THE
 SWITCH MEETS 13-415.1.ABC.1.4. THERE ARE TWO TYPES OF
 CONTROLS REQUIRED. BASED ON THE ELECTRICAL RISER AND
 INFORMATION SHOWN ON PLANS THIS DOES NOT MEET EITHER.
 PLEASE KNOW AN ASTRONOMICAL TIME CLOCK W/ A MINIMUM OF
 10HR BACK UP FOR PROGRAMMING OR PHOTO-SENSOR IS THE TWO
 OPTIONS.
  
 3) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]