Plan Review Notes
Plan Review Notes For Permit 08010276
Permit Number 08010276
Review Stop P
Sequence Number 2
Notes
Date Text
2008-04-04 11:22:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2004 FUEL GAS
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES.
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. SHT 1 OF 2 THE GREASE INTERCEPTOR UNDER THE SINK IS
 NOT APPROVED. A MINIMUM 750 GAL. GREASE INTERCEPTOR IS
 REQUIRED. PLEASE CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE AT (561) 644-1821, (FAX) - (561) 822-2272 -
 OR E-MAIL [email protected]. A WRITTEN DETERMINATION IS
 REQUIRED TO BE SUBMITTED FOR APPROVAL OF THE GREASE
 INTERCEPTOR WHEN RESUBMITTING TO THE CITY FOR REVIEW.
 WPB MUNICIPAL CODE ARTICLE III SECTION
 90-124(7)(B)(C)(E)(F).
 ****RESPONSE NOTED, BUT THE WRITTEN APPROVAL FROM MR.
 RODNEY COMPO HAS NOT BEEN SUBMITTED.
  
 5. OK
 6. OK
  
 7. SHT 2 OF 2 RISER #2 THE GREASE INTERCEPTOR IS NOT
 APPROVED INSIDE. A MINIMUM 750 GALLON GREASE
 INTERCEPTOR IS REQUIRED. (SEE COMMENT #4). THE MOB SINK
 SHALL CONNECT TO THE GREASE SYSTEM.
 ****RESPONSE NOTED, BUTTHE WRITTEN APPROVAL FROM MR.
 RODNEY COMPO HAS NOT BEEN SUBMITTED.
  
 8. OK
  
 9. THE FLOOR DRAIN BY THE COOLER IS NOT VENTED. MAXIMUM
 DISTANCE FROM POINT OF VENT IS 10 FEET. TABLE
 906.1.****RESPONSE NOTED, BUT THE FLOOR SINK IS NOT
 VENTED PER TABLE 906.1. A WET VENT IS FOR BATHROOM
 FIXTURES ONLY AND "WET VENT" IS NOT IN THE DEFINITIONS
 IN SECTION 202. PLEASE CLARIFY THE MEANING OF THE
 RESPONSE. SEE WET VENT:909.1 WET VENT PERMITTED. ANY
 COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE
 CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE
 FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved