| Date |
Text |
| 2008-04-04 11:22:36 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2004 FUEL GAS |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES. |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. SHT 1 OF 2 THE GREASE INTERCEPTOR UNDER THE SINK IS |
| | NOT APPROVED. A MINIMUM 750 GAL. GREASE INTERCEPTOR IS |
| | REQUIRED. PLEASE CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE AT (561) 644-1821, (FAX) - (561) 822-2272 - |
| | OR E-MAIL [email protected]. A WRITTEN DETERMINATION IS |
| | REQUIRED TO BE SUBMITTED FOR APPROVAL OF THE GREASE |
| | INTERCEPTOR WHEN RESUBMITTING TO THE CITY FOR REVIEW. |
| | WPB MUNICIPAL CODE ARTICLE III SECTION |
| | 90-124(7)(B)(C)(E)(F). |
| | ****RESPONSE NOTED, BUT THE WRITTEN APPROVAL FROM MR. |
| | RODNEY COMPO HAS NOT BEEN SUBMITTED. |
| | |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT 2 OF 2 RISER #2 THE GREASE INTERCEPTOR IS NOT |
| | APPROVED INSIDE. A MINIMUM 750 GALLON GREASE |
| | INTERCEPTOR IS REQUIRED. (SEE COMMENT #4). THE MOB SINK |
| | SHALL CONNECT TO THE GREASE SYSTEM. |
| | ****RESPONSE NOTED, BUTTHE WRITTEN APPROVAL FROM MR. |
| | RODNEY COMPO HAS NOT BEEN SUBMITTED. |
| | |
| | 8. OK |
| | |
| | 9. THE FLOOR DRAIN BY THE COOLER IS NOT VENTED. MAXIMUM |
| | DISTANCE FROM POINT OF VENT IS 10 FEET. TABLE |
| | 906.1.****RESPONSE NOTED, BUT THE FLOOR SINK IS NOT |
| | VENTED PER TABLE 906.1. A WET VENT IS FOR BATHROOM |
| | FIXTURES ONLY AND "WET VENT" IS NOT IN THE DEFINITIONS |
| | IN SECTION 202. PLEASE CLARIFY THE MEANING OF THE |
| | RESPONSE. SEE WET VENT:909.1 WET VENT PERMITTED. ANY |
| | COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE |
| | VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED |
| | THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE |
| | CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE |
| | FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE |
| | DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY |
| | THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |