2008-03-20 09:19:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE ENERGY CALCULATIONS NEED TO BE GENERATED BY THE
 FLA/COM-2004 COMPUTER PROGRAM, VERSION 2.5 NOT 3.0, ON
 FORM 400B-04, PER 2004 FBC 13-400.3.B. PLEASE CORRECT.
  
 2) WHEN RESUBMITTING ENERGY CALCULATIONS HAVE THEM
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC 13-103.3.
  
 3) THE COOLING LOAD CALCULATIONS ARE MISSING FROM THE
 ENERGY CAL'S. PLEASE SUBMITCOOLING LOAD CALCULATIONS,
 PER 2004 FBC 13-407.1.ABC.1.
  
 4) THE PLANS AND ENERGY CALCULATIONS ARE SHOWING THE
 WRONG ADDRESS THE BUILDING NUMBER IS 5910 S. DIXIE HWY.
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]