Plan Review Notes
Plan Review Notes For Permit 08010276
Permit Number 08010276
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-20 16:28:00** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE VERSION OF THE SUBMITTED ENERGY
 CALCULATIONS IS NOT CORRECT. PLEASE SEE 13-400.3.B AS
 THIS SHOULD BE VERSION 2.5.
 PLEASE BE SURE THE OWNER AGENT SIGNATURE IS SIGNED ON
 CERTIFICATION SHEET.13-103.1.1.1
  
 2) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS ON PLANS NOTE MENTIONS DISPLAY AND ACCENT
 LIGHTING IS NOT INCLUDED PER SECTIONS 13-415.B.1 AND
 13-415.2.C.1.
 PLEASE SEE 13-415.2.ABC.1 EXCEPTIONS AS DISPLAY AND
 ACCENT LIGHTING FOR THIS OCCUPANCY AND USE AS
 SPECIFICALLY SHOWN ON PLANS IS NOT EXEMPT.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 FOR
 INTERIOR LIGHTING ALLOWANCES.
 PLEASE SEE THE IDR SHALL COORDINATE WITH PLANS.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF
 EXTERIOR LIGHT(S). PHOTO-SENSOR OR ASTRONOMICAL TIME
 CLOCK WITH A MINIMUM OF 10HRS BATTERY BACK UP FOR
 PROGRAMMING. PLEASE SHOW WHICH IS BEING USED, OR UNLESS
 BOTH ARE BEING INSTALLED.
 PLANS ONLY SHOW SINGLE POLE SWITCH.
  
 4) NOTE: PLEASE PROVIDE MAXIMUM TIMES ON ALL OVER RIDES
 DEVICES PER 13-415.1.ABC.1.1 AND OTHER OCCUPANCY SENSOR
 TYPE DEVICES.
  
 5) NOTE: PLEASE SEE THE ADDRESS ON PLANS AND ENERGY
 CALCULATIONS ARE INCORRECT.
 PLEASE SEE THE APPLIED LOCATION IS 5910 S. DIXIE HWY,
 YET ALL DOCUMENTS STATE 5908?
 PLEASE GET WITH THE ADDRESSING REVIEWER FOR FINAL
 DETERMINATION. IF A SUITE OR UNIT NUMBER IS TO BE
 GENERATED OR ADDRESS IS MODIFIED, THEN PLEASE BE SURE
 ALL TITLE BLOCKS AND DOCUMENTS ARE ADJUSTED.
 FAC 61G1-16.004, 61G15-23.002
  
 6) NOTE: PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS. DO NOT LEAVE OLD SHEETS IN NEW SETS. PLEASE
 ALSO BE SURE NOT TO ATTACH SUPPORTING DOCUMENTS DOWN
 THE LEFT HAND SIDE OF PLANS.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID DELAYS.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  