| 2008-03-20 16:28:00 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE VERSION OF THE SUBMITTED ENERGY |
| | CALCULATIONS IS NOT CORRECT. PLEASE SEE 13-400.3.B AS |
| | THIS SHOULD BE VERSION 2.5. |
| | PLEASE BE SURE THE OWNER AGENT SIGNATURE IS SIGNED ON |
| | CERTIFICATION SHEET.13-103.1.1.1 |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS ON PLANS NOTE MENTIONS DISPLAY AND ACCENT |
| | LIGHTING IS NOT INCLUDED PER SECTIONS 13-415.B.1 AND |
| | 13-415.2.C.1. |
| | PLEASE SEE 13-415.2.ABC.1 EXCEPTIONS AS DISPLAY AND |
| | ACCENT LIGHTING FOR THIS OCCUPANCY AND USE AS |
| | SPECIFICALLY SHOWN ON PLANS IS NOT EXEMPT. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 FOR |
| | INTERIOR LIGHTING ALLOWANCES. |
| | PLEASE SEE THE IDR SHALL COORDINATE WITH PLANS. |
| | |
| | 3) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF |
| | EXTERIOR LIGHT(S). PHOTO-SENSOR OR ASTRONOMICAL TIME |
| | CLOCK WITH A MINIMUM OF 10HRS BATTERY BACK UP FOR |
| | PROGRAMMING. PLEASE SHOW WHICH IS BEING USED, OR UNLESS |
| | BOTH ARE BEING INSTALLED. |
| | PLANS ONLY SHOW SINGLE POLE SWITCH. |
| | |
| | 4) NOTE: PLEASE PROVIDE MAXIMUM TIMES ON ALL OVER RIDES |
| | DEVICES PER 13-415.1.ABC.1.1 AND OTHER OCCUPANCY SENSOR |
| | TYPE DEVICES. |
| | |
| | 5) NOTE: PLEASE SEE THE ADDRESS ON PLANS AND ENERGY |
| | CALCULATIONS ARE INCORRECT. |
| | PLEASE SEE THE APPLIED LOCATION IS 5910 S. DIXIE HWY, |
| | YET ALL DOCUMENTS STATE 5908? |
| | PLEASE GET WITH THE ADDRESSING REVIEWER FOR FINAL |
| | DETERMINATION. IF A SUITE OR UNIT NUMBER IS TO BE |
| | GENERATED OR ADDRESS IS MODIFIED, THEN PLEASE BE SURE |
| | ALL TITLE BLOCKS AND DOCUMENTS ARE ADJUSTED. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 6) NOTE: PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS. DO NOT LEAVE OLD SHEETS IN NEW SETS. PLEASE |
| | ALSO BE SURE NOT TO ATTACH SUPPORTING DOCUMENTS DOWN |
| | THE LEFT HAND SIDE OF PLANS. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID DELAYS. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |