| 2008-02-11 19:12:13 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2004 FUEL GAS |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES. |
| | |
| | 1. PLEASE INDICATE THE RELEVANT CODES ON PLANS. |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE, |
| | (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE |
| | TITLE BLOCK OF EACH SHEET. FAC 61G1-16.219, |
| | 61G1-16.004(2) & FS 481.2055. |
| | |
| | 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF |
| | BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND |
| | RESTAURANT FOOD SERVICE LICENSE PRIOR TO RESUBMITTING |
| | TO THE CITY FOR REVIEW. A MINIMUM TWO SETS OF PLANS |
| | CONTAINING THE DBPR STAMPED, (REVIEWED) SHEET AND THE |
| | SPECIFICATION WORK SHEETS SHALL BE SUBMITTED FOR |
| | REVIEW. SECTION 102.2.1. |
| | |
| | 4. SHT 1 OF 2 THE GREASE INTERCEPTOR UNDER THE SINK IS |
| | NOT APPROVED. A MINIMUM 750 GAL. GREASE INTERCEPTOR IS |
| | REQUIRED. PLEASE CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE AT (561) 644-1821, (FAX) - (561) 822-2272 - |
| | OR E-MAIL [email protected]. A WRITTEN DETERMINATION IS |
| | REQUIRED TO BE SUBMITTED FOR APPROVAL OF THE GREASE |
| | INTERCEPTOR WHEN RESUBMITTING TO THE CITY FOR REVIEW. |
| | WPB MUNICIPAL CODE ARTICLE III SECTION |
| | 90-124(7)(B)(C)(E)(F). |
| | |
| | 5. SHT 2 OF 3 EQUIPMENT SCHEDULE INDICATES A GAS WATER |
| | HEATER, 70,000 BTU'S, BUT SHT 1 OF 2 DOES NOT SHOW |
| | THIS. PLEASE CLARIFY & CORRELATE THE PLANS. SECTION |
| | 106.1.1. |
| | |
| | 6. SHT 2 OF 2 DETAIL 2, FLOOR DRAINS ARE NOT APPROVED |
| | INDIRECT WASTE RECEPTORS. A FLOORSINK OR HUB DRAIN IS |
| | REQUIRED. SECTIONS 802.3 & 802.3.2. |
| | |
| | 7. SHT 2 OF 2 RISER #2 THE GREASE INTERCEPTOR IS NOT |
| | APPROVED INSIDE. A MINIMUM 750 GALLON GREASE |
| | INTERCEPTOR IS REQUIRED. (SEE COMMENT #4). THE MOB SINK |
| | SHALL CONNECT TO THE GREASE SYSTEM. |
| | |
| | 8. SHT 2 OF 2 FLOOR DRAIN BY THE COOLER IS NOT AN |
| | APPROVED INDIRECT WASTE INTERCEPTOR. A FLOORSINK OR |
| | HUB DRAIN IS REQUIRED. SECTIONS 802.3 & 802.3.2. |
| | |
| | 9. THE FLOOR DRAIN BY THE COOLER IS NOT VENTED. MAXIMUM |
| | DISTANCE FROM POINT OF VENT IS 10 FEET. TABLE 906.1. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |