| Date |
Text |
| 2008-02-20 14:58:00 | *****DENIED***** |
| | |
| | |
| | 01.THE ADDRESS (5908 SO. DIXIE) SHOWN IN THE TITLE |
| | BLOCK OF THE SUBMITTED PLAN SHEETS DOES NOT MATCH THAT |
| | OF 5910 SO. DIXIE AS PER THE APPLIED PERMIT LOCATION. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE PREMISES AT THE END OF EACH |
| | SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE |
| | OPERATION. |
| | |
| | 04.POST/DISPLAY THE NUMERICAL ADDRESS ON THE |
| | APPROPIATE ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY. |
| | AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO |
| | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | WIDTH/STROKE.ADDRESS NUMBERS ARE NOT ALLOWED ON THE |
| | FRONT DOOR, HOWEVER IF THIS STRUCTURE IS PART OF AN |
| | ATTACHED BUILDING, ADDRESS NUMBER OF 3" IN HEIGHT SHALL |
| | BE REQUIRED ON THE REAR DOOR. |
| | |
| | 05.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 06.PLEASE INDICATE THE FOLLOWING FOR THE STRUCTURE: * |
| | OCCUPANCY TYPE AND USE,* OCCUPANT LOAD,* FIRE ALARM |
| | AND/OR FIRE SPRINKLER SYSTEM,*AND ANY OTHER PERTINENT |
| | BUILDING INFORMATION |
| | |
| | 07.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE. |
| | |
| | 08.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 09.COMMERCIAL COOKING EQUIPMENT SHALL BE IN |
| | ACCORDANCE WITH NFPA 96.SEPARATE PLANS AND PERMIT |
| | WILL BE REQUIRED FOR BOTH THE COOKING HOOD'S |
| | INSTALLATION AND THE COOKING HOOD'S SUPPRESSION |
| | SYSTEM. |
| | |
| | 10.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM AS PER LOCAL REQUIREMENTS.IF THE BUILDING IS |
| | NOT EQUIPPED WITH A FIRE ALARM SYSTEM, HOW WILL THE |
| | INITIATIATION OF A DUCT DETECTOR ACHIEVE OCCUPANT |
| | AND/OR EMERGENCY FORCES NOTIFICATION. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |