Plan Review Notes
Plan Review Notes For Permit 08010276
Permit Number 08010276
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-17 08:36:11** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT PLANS WITH THE FOLLOWING
 RELEVANT CODES STATED AND SHOWN ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE ARCHITECTURAL PLANS ALONG WITH
 OTHER SHEETS WHICH CONTAIN A TITLE BLOCK FOR
 ARCHITECTURAL FIRM HOWEVER DOES NOT CONTAIN THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE 61G1-16.004 AND FS 481.219 WHICH BOTH
 REQUIRE THIS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENTS ARE MADE BY OTHER TRADES.
 ** PLEASE SEE POSSIBLE NOTES FROM OTHER TRADES WITH
 RESPECT TO *SIGNATURE* REQUIRED ON ARCHITECTRUAL
 SHEETS.
  
 3) NOTE: PLEASE CLARIFY HOW IT IS THE PLANS ARE BEING
 SUBMITTED WITH METHOD A ENERGY CALCULATIONS.???
 PLEASE SEE THIS IS NOT A WHOLE BUILDING AND IS ONLY A
 TENANT REMODEL IN AN EXISTING BUILDING. THE SCOPE OF
 WORK IS NOT FOR THE BUILDING BY DEFINITION.
 PLEASE SEE THE LIGHTING PLANS INCLUDE A SPACE BY SPACE
 METHOD *B* IN NOTES, YET THE CALCULATIONS ARE NOT SPACE
 BY SPACE.??
 PLEASE SEE THE NOTE ON THIS SAME CALCULATION STATES
 FIXTURES *C* AND *B* ARE NOT INCLUDED. HOW IS THIS
 POSSIBLE?
 PLEASE SEE 13-415.2
 PLEASE ADJUST CALCULATIONS. PLEASE KNOW AS METHOD *A*
 CAN NOT BE USED, IT IS NOT REQUIRED FOR ELECTRICAL
 REVIEW. PLEASE CONFIRM WHAT IS NEEDED FROM THE
 MECHANICAL REVIEWER.
  
 4) NOTE: PLEASE KNOW THE SIGN(S) FOR EXTERIOR OF
 BUILDING IS REQUIRED TO BE UNDER SEPARATE PERMITS.
  
 5) NOTE: PLEASE INDICATE AIC RATINGS FOR NEW MAINS.
 110.9
  
 6) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTOR
 SHOWN BEFORE THE FIRST MEANS OF DISCONNECT IS NOT
 PERMITTED.
 PLEASE SEE 250.6, 250.24.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.