| 2008-01-26 17:21:02 | BUILDING PLAN REVIEW |
| | PERMIT: 08010276 |
| | ADD: 5910 S DIXIE HWY SUITE# 5908 |
| | CONT: ABBATE BUILDING CO |
| | TEL: (772)501-1420 |
| | JAN26, 2008 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS. |
| | |
| | 2) JOHN D. CONLEY INC DOES NOTPROVIDE THEIR |
| | CERTIFICATE OF AUTHORIZATION, PLEASE PROVIDE.481.219 |
| | F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK |
| | FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD |
| | THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND. |
| | |
| | 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) 2004 FBC EXISTING BUILDING CODE, WHAT LEVEL OF |
| | ALTERATION IS TO BE CONSIDERED, IF LEVEL II SEE CHAPTER |
| | 6 FOR LEVEL II ALTERATIONS. |
| | C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | D) IS THIS A FIRE SPRINKLED BUILDING? |
| | |
| | 4) SHEET 3OF 3 FRONT COUNTER ELEVATION DOES NOT |
| | INDICATE THE HEIGTH THE COUNTER, PLEASE PROVIDE |
| | COMPLIANCE WITH: 11-5.2 COUNTERS AND BARS WHERE FOOD OR |
| | DRINK IS SERVED @ COUNTERS EXCEEDING 34" IN HEIGHT FOR |
| | CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING |
| | AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS |
| | 60" IN LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE |
| | WITH 11-4.32 OR SERVICE SHALL BE AVAILABLE AT |
| | ACCESSIBLE TABLES WITHIN THE SAME AREA. |
| | |
| | 5) PLANS INDICATE A NEW 5TON RTU-2 UNIT BUT NO |
| | INFORMATION WAS SUPPLIED AS TO THE ADDITIONAL LOADING |
| | TO THE ROOF FRAMING MEMBERS, NEW CURB ATTACHMENT, |
| | PLEASE PROVIDE ANCHORING INFORMATION FOR CURB AND POINT |
| | LOADING OF ROOF FRAMING MEMBERS, ADDITIONAL INFORMATION |
| | REQUIRED, 106.1.2 AND 1609.1.3 ANCHORAGE AGAINST |
| | OVERTURNING, UPLIFT AND SLIDING. |
| | |
| | 6)PLANS INDICATE A NEW WALK IN COOLER, PLEASE INDICATE |
| | THE LOCATION OF THE COMPRESSOR. IF LOCATED ON THE ROOF |
| | ON A NEW PREMANUFACTURED A/C STAND THE FOLLOWING |
| | REQUIREMENTS ARE TO BE MET: |
| | 6A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES,3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: PREMANUFACTURED A/C STANDS |
| | |
| | 6B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) PLEASE PROVIDE INFORMATION ON THE WALK IN COOLER, |
| | THICKNESS OF FOAM, FLAME SPREAD AND THICKNESS OF THE |
| | METAL FACINGMATERIALS OF COOLER, SECTION 2603.4.1.3. |
| | |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |