Plan Review Notes
Plan Review Notes For Permit 08010276
Permit Number 08010276
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-26 17:21:02BUILDING PLAN REVIEW
 PERMIT: 08010276
 ADD: 5910 S DIXIE HWY SUITE# 5908
 CONT: ABBATE BUILDING CO
 TEL: (772)501-1420
 JAN26, 2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) JOHN D. CONLEY INC DOES NOTPROVIDE THEIR
 CERTIFICATE OF AUTHORIZATION, PLEASE PROVIDE.481.219
 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK
 FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) 2004 FBC EXISTING BUILDING CODE, WHAT LEVEL OF
 ALTERATION IS TO BE CONSIDERED, IF LEVEL II SEE CHAPTER
 6 FOR LEVEL II ALTERATIONS.
 C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 D) IS THIS A FIRE SPRINKLED BUILDING?
  
 4) SHEET 3OF 3 FRONT COUNTER ELEVATION DOES NOT
 INDICATE THE HEIGTH THE COUNTER, PLEASE PROVIDE
 COMPLIANCE WITH: 11-5.2 COUNTERS AND BARS WHERE FOOD OR
 DRINK IS SERVED @ COUNTERS EXCEEDING 34" IN HEIGHT FOR
 CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING
 AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS
 60" IN LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 5) PLANS INDICATE A NEW 5TON RTU-2 UNIT BUT NO
 INFORMATION WAS SUPPLIED AS TO THE ADDITIONAL LOADING
 TO THE ROOF FRAMING MEMBERS, NEW CURB ATTACHMENT,
 PLEASE PROVIDE ANCHORING INFORMATION FOR CURB AND POINT
 LOADING OF ROOF FRAMING MEMBERS, ADDITIONAL INFORMATION
 REQUIRED, 106.1.2 AND 1609.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIDING.
  
 6)PLANS INDICATE A NEW WALK IN COOLER, PLEASE INDICATE
 THE LOCATION OF THE COMPRESSOR. IF LOCATED ON THE ROOF
 ON A NEW PREMANUFACTURED A/C STAND THE FOLLOWING
 REQUIREMENTS ARE TO BE MET:
 6A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS: PREMANUFACTURED A/C STANDS
  
 6B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) PLEASE PROVIDE INFORMATION ON THE WALK IN COOLER,
 THICKNESS OF FOAM, FLAME SPREAD AND THICKNESS OF THE
 METAL FACINGMATERIALS OF COOLER, SECTION 2603.4.1.3.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.