2008-01-15 12:05:12*** PROVISO ***
 1) PER 2004 FBC/M 607.5.3 DUCT PENETRATIONS IN FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING, OR
 MEET THE EXCEPTIONS.
  