Plan Review Notes
Plan Review Notes For Permit 08010268
Permit Number 08010268
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-15 18:07:48** PROVISO **
  
 ** PLEASE SUBMIT THE BELOW REVISED INFORMATION FOR
 COMMENT NUMBER ONE BEFORE ROUGH ELECTRICAL INSPECTION.
  
 ** PLEASE SEE THE REVISED INFORMATION FOR COMMENT #2
 MAY BE DONE BEFORE FINAL.
  
 ** ALL REVISED AND STAMPED PLANS ARE REQUIRED TO BE
 ON-SITE FOR THE ELECTRICAL INSPECTOR AT TIME OF
 INSPECTION.
  
 1) NOTE: PLEASE SUBMIT REVISED LIGHTING FIXTURE LEGEND
 PROVIDING MORE DETAILED INFORMATION ON FIXTURES.
 FBC CHAPTER 13. 13-415.2,FBC 106.1.2
  
 2) NOTE: PLEASE PROVIDE AN UPDATED PANEL SCHEDULE WHERE
 THE PANEL SCHEDULE IS SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED. FOR EXAMPLE: CIRCUIT 5LA-9CONF. ROOM
 ETC
 408.4,
 FBC 16.1.2, 106.3.5.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  