| 2008-01-16 16:21:22 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 08010268 |
| | ADD: 1675 PBL BLVD #500 |
| | CONT: MJS CONSTRUCTION INC. |
| | TEL: (561)615-9348 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2)FBC 1210.2THE WALLS WITHIN 2 FEET OF URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FINISH FLOOR. |
| | PAINT ON DRYWALL IS NOT CONSIDERED AN HARD SURFACE. |
| | INDICATE HOW THIS SECTION OF THE CODE WILL BE MET ON |
| | THE DRAWINGS. |
| | |
| | 3)PROVIDE A FRAMING DETAIL FOR THE DRYWALL CEILING IN |
| | CONFERENCE ROOM #501. INDICATE THE STUD SPACING, AND |
| | ALL OTHER MATERIALS. DETAIL A8 ON SHEET A3.2 DOES NOT |
| | STATE THE TYPE OF MATERIALS WHICH WILL BE USED TO |
| | CONSTRUCT THE 4 FOOT WALL. THE STUD SPACING SHALL BE |
| | INDICATED FOR THESE WALLS. A DETAIL FOR THE 60 INCHES |
| | WALLS SHALL ALSO BE PROVIDED. ADDITIONAL DETAILS, |
| | INFORMATION AND DIAGRAMS ARE REQUIRED FOR THESE TWO |
| | WALLS TO SHOW CLARITY PER WPB AMENDMENTS 106.1.2. |
| | |
| | 4)FBC 11-4.24.5 A CLEAR FLOOR SPACE (30 X 48) SHALL |
| | BE PROVIDED IN FRONT OF THE BREAK ROOM SINK TO ALLOW |
| | FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON THE |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES UNDERNEATH THE SINK. A FRONT ELEVATION DETAIL OF |
| | THE CABINETS AND THE SINK CAN BE SUBMITTED SHOWING |
| | COMPLIANCE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |