| 2008-01-29 11:51:39 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS AS RISER |
| | HAS NOW BEEN REVISED ONCE AGAIN WITH ITEMS WHICH WAS |
| | NOT ON PREVIOUS PLANS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE A ?COVER SHEET STILL INDICATE |
| | SUITE/UNIT SCOPE OF WORK FOR SUITE/UNIT #102. AS THIS |
| | APPLIED SCOPE OF WORK IS FOR ANOTHER SUITE/UNIT SPACE |
| | PLEASE ADJUST COVER SHEET. |
| | PLEASE KNOW THE ADDRESS EXTENSION OF PROJECT HAS NOT |
| | YET BEEN CONFIRMED WITH THE ADDRESSING REVIEWER. PLEASE |
| | KEEP IN MIND ANY CHANGES BASED ON THEIR REVIEW MAY |
| | REQUIRE TITLE BLOCK ADJUSTMENTS ON OTHER SHEETS. FAC |
| | 61G1-16.004, 61G15-23.002 |
| | FBC 106.5, 106.1.2 ADMIN SECTION. |
| | |
| | 2) NOTE: PLEASE SEE AS MENTIONED AND NOTED ON PREVIOUS |
| | REVIEW TO LOCATIONS OF MAINS AS PER 230.72. THIS WAS |
| | NOT DONE. THE NEW MAIN CIRCUIT BREAKER PANEL FOR SUITE |
| | # 101 IS SHOWN INSIDE THE UNIT WITH NO MAIN GROUPED |
| | WITH OTHER MAINS OR LABELED AS REQUIRED PER 230.72, |
| | 230.70, 230.71, 230.2E ETC. |
| | |
| | 3) NOTE: PLEASE SEE THE LOAD CALCULATIONS NOTES AND |
| | MENTIONS CONDUCTORS FOR SERVICE ENTRANCE ARE RATED FOR |
| | 385AMPS EACH PHASE HOWEVER BASED ON THE MINIMUM |
| | REQUIREMENTS AND CONDUCTOR AMPACITIES IN THE NATIONAL |
| | ELECTRICAL CODE AS WELL AS THE ADOPTED AWG STANDARD. |
| | THE 350MCM CONDUCTORS ARE NOT RATED FOR 385AMPS. PLEASE |
| | SEE 110.14, 310.16 AND 240.4. |
| | PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AS SHOWN |
| | SHALL BE INCREASED. |
| | |
| | 4) NOTE: PLEASE SEE RISER CONTAINS NOTES FOR EXISTING |
| | SUITE/UNIT #102 HOWEVER NOT SUCH SAME NOTES ARE SHOWN |
| | FOR NEW SUITE/UNIT #101. |
| | PLEASE SEE THE BOTTOM RIGHT HAND CORNER OF THE RISER |
| | SHEET E-2. |
| | PLEASE COMPLETE WITH NEW, SAME OR EXISTING |
| | INFORMATION. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 5) NOTE: PLEASE SEE THE LOCATION OF THE SIGN CIRCUIT |
| | WAS NOT SHOWN. PER 600.5 |
| | |
| | ** AS SOME ITEMS ARE GOING TO CHANGE SUBSTANTIALLY, |
| | THERE MAY BE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |