Plan Review Notes
Plan Review Notes For Permit 08010251
Permit Number 08010251
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-29 11:51:39** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS AS RISER
 HAS NOW BEEN REVISED ONCE AGAIN WITH ITEMS WHICH WAS
 NOT ON PREVIOUS PLANS.
  
  
  
 1) NOTE: PLEASE SEE THE A ?COVER SHEET STILL INDICATE
 SUITE/UNIT SCOPE OF WORK FOR SUITE/UNIT #102. AS THIS
 APPLIED SCOPE OF WORK IS FOR ANOTHER SUITE/UNIT SPACE
 PLEASE ADJUST COVER SHEET.
 PLEASE KNOW THE ADDRESS EXTENSION OF PROJECT HAS NOT
 YET BEEN CONFIRMED WITH THE ADDRESSING REVIEWER. PLEASE
 KEEP IN MIND ANY CHANGES BASED ON THEIR REVIEW MAY
 REQUIRE TITLE BLOCK ADJUSTMENTS ON OTHER SHEETS. FAC
 61G1-16.004, 61G15-23.002
 FBC 106.5, 106.1.2 ADMIN SECTION.
  
 2) NOTE: PLEASE SEE AS MENTIONED AND NOTED ON PREVIOUS
 REVIEW TO LOCATIONS OF MAINS AS PER 230.72. THIS WAS
 NOT DONE. THE NEW MAIN CIRCUIT BREAKER PANEL FOR SUITE
 # 101 IS SHOWN INSIDE THE UNIT WITH NO MAIN GROUPED
 WITH OTHER MAINS OR LABELED AS REQUIRED PER 230.72,
 230.70, 230.71, 230.2E ETC.
  
 3) NOTE: PLEASE SEE THE LOAD CALCULATIONS NOTES AND
 MENTIONS CONDUCTORS FOR SERVICE ENTRANCE ARE RATED FOR
 385AMPS EACH PHASE HOWEVER BASED ON THE MINIMUM
 REQUIREMENTS AND CONDUCTOR AMPACITIES IN THE NATIONAL
 ELECTRICAL CODE AS WELL AS THE ADOPTED AWG STANDARD.
 THE 350MCM CONDUCTORS ARE NOT RATED FOR 385AMPS. PLEASE
 SEE 110.14, 310.16 AND 240.4.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AS SHOWN
 SHALL BE INCREASED.
  
 4) NOTE: PLEASE SEE RISER CONTAINS NOTES FOR EXISTING
 SUITE/UNIT #102 HOWEVER NOT SUCH SAME NOTES ARE SHOWN
 FOR NEW SUITE/UNIT #101.
 PLEASE SEE THE BOTTOM RIGHT HAND CORNER OF THE RISER
 SHEET E-2.
 PLEASE COMPLETE WITH NEW, SAME OR EXISTING
 INFORMATION.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS FOR ADDITIONAL
 INFORMATION.
  
 5) NOTE: PLEASE SEE THE LOCATION OF THE SIGN CIRCUIT
 WAS NOT SHOWN. PER 600.5
  
 ** AS SOME ITEMS ARE GOING TO CHANGE SUBSTANTIALLY,
 THERE MAY BE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]