| Plan Review Notes For Permit 08010251 |
| Permit Number |
08010251 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-15 11:13:09 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) THE BATHROOMS ON THE MECHANICAL PLAN PAGE M-1 WILL | | | REQUIRE EXHAUST FANS, SEE 2004 FBC/M 403.2 (3). PLEASE | | | CORRECT. | | | | | | 2) PLEASE SHOW THE CFM'S AND GRILL SIZES AT ALL SUPPLY | | | AIR GRILLS ON THE MECHANICAL PLAN, SEE 2004 FBC | | | 106.3.5 | | | | | | 3) THE OUTSIDE AIR CALCULATIONS ON THE MECHANICAL PLAN | | | SHOWS 1,644 CFM'S, AND THE EQUIPMENT SCHEDULE SHOWS 500 | | | CFM'S. THE TWO MUST COINCIDE, SEE 2004 FBC/M 403.3. | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|