2008-01-15 11:13:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE BATHROOMS ON THE MECHANICAL PLAN PAGE M-1 WILL
 REQUIRE EXHAUST FANS, SEE 2004 FBC/M 403.2 (3). PLEASE
 CORRECT.
  
 2) PLEASE SHOW THE CFM'S AND GRILL SIZES AT ALL SUPPLY
 AIR GRILLS ON THE MECHANICAL PLAN, SEE 2004 FBC
 106.3.5
  
 3) THE OUTSIDE AIR CALCULATIONS ON THE MECHANICAL PLAN
 SHOWS 1,644 CFM'S, AND THE EQUIPMENT SCHEDULE SHOWS 500
 CFM'S. THE TWO MUST COINCIDE, SEE 2004 FBC/M 403.3.
 PLEASE CORRECT.
  