| 2008-10-31 15:46:24 | REVISION FAILED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P-203A INDICATES 3 GAS DRYERS, BUT ONLY 2 GAS |
| | DRYERS ARE SHOWN. NO CHANGE IN DRYER AMOUNTS SHOWN ON |
| | FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 & 402.1. |
| | |
| | 2. SHT P-500 THE FLOOR DRAINS (3) ADDED NEAR THE BASE |
| | OF STACK SAN-13 AND BY THE TOILET ROOMS FOR THE SPA'S |
| | ARE NOT VENTED. SECTIONS 901.2.1 & 908.3. |
| | |
| | 3. SHT P-501 THE SANITARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE WASH MACHINES FOR THE |
| | GUEST LAUNDRY ROOM. THE TRAP & LAUNDRY BOX ARE SHOWN ON |
| | EACH SIDE OF THE STACK ON THE FLOOR PLAN, BUT ARE SHOWN |
| | ON ONE SIDE OF THE STACK ON THE RISER DIAGRAM. ALSO THE |
| | SECOND TRAP IS NOT SHOWN CONNECTING TO THE STACK. |
| | SECTIONS 106.1.1 & 706.3. |
| | |
| | 4. SHT P-503 REVISION #4 HAS BEEN DELETED FROM THE |
| | REVISION INDEX. PLEASE KEEP ALL PREVIOUS REVISION |
| | NUMBERS IN INDEX THROUGH OUT THE PERMIT CYCLE. NO NEW |
| | CHANGES INDICATED ON THE SHEET AS REVISION #5. IF NO |
| | CHANGES/REVISIONS NOT REQUIRED FOR PUBLIC RECORD. |
| | SECTION 106.1.3. |
| | |
| | 5. SHT P-602 NATURAL GAS SIZING TABLE. NOT ALL CHANGES |
| | HAVE BEEN INDICATED WITH A CLOUD OR REVISION NUMBER. |
| | SEE SECTION LOAC (CFH) FOR A, J, K & L AS WELL AS APPL |
| | LOAD (CFH) FOR J. PIPE SECTION N SECTION LOAD TO BE 700 |
| | AND THE LONGEST RUN TO BE SECTION P, NOT O. PLEASE |
| | CORRELATE ALL CHANGES TO NATURAL GAS SIZING TABLE AND |
| | CLOUD ALL REVISIONS AND INDICATE WITH A REVISION |
| | NUMBER. SECTION 106.1.3. |
| | |
| | 6. SHT P-602 GAS RISER DIAGRAM INDICATES SECTION P TO |
| | BE 1/2", BUT IT ALSO SHOWS 3/4" GAS VALVE AND CAP. |
| | PLEASE CLARIFY. SECTIONS 106.1.1 AND 402.1. |
| | |
| | 7. SHT P-602 GAS RISER DIAGRAM DOES NOT SHOW SECTION O. |
| | PLEASE CORRELATE WITH GAS SIZING TABLE. SECTIONS |
| | 106.1.1 & 402.1. |
| | |
| | 8. SHT P-602 GAS RISER DIAGRAM. UNIONS ARE REQUIRED |
| | DOWNSTREAM OF THE SHUT OFF VALVES FOR EACH REGULATOR AT |
| | THE WATER HEATERS AND THE POOL HEATER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |