| Plan Review Notes For Permit 08010249 |
| Permit Number |
08010249 |
|
| Review Stop |
E |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2009-01-29 17:51:43 | SUBMITTAL FOR GENERATOR AND ATS DEVICES. | | | REDLINED THE *EMERGENCY DISCONNECT* IN SUBMITTED. THE | | | GLASS TYPE SHUNT TRIP IS NOT A RATED DISCONNECT. THE | | | DISCONNECTTING MEANS RATED FOR THE LOAD SERVED IS | | | LOCATED ON RISER. SHOWN ON EMDP,EDPLS AND EACH BREAKER | | | ON THE GENERATOR. THIS GLASS BREAK TYPE OF BUTTON IS IN | | | ADDITION TO THE RATED DISCONNECTS AS SHOWN. | | | 230.76,230.79,225.39 ETC |
|