| Date |
Text |
| 2008-11-07 10:12:41 | ** DENIED REVISIONS ** |
| | |
| | ** A CALLED WAS PLACED TO ENGINEER ON 11/6/08 IN THE |
| | AFTERNOON HOWEVER HE WAS OUT OF THE OFFICE. SOME OF |
| | THESE ITEMS WILL NEED TO BE GONE OVER. |
| | |
| | ** THANK YOU FOR NARRATIVE ON REVISIONS. IT IS MOST |
| | HELPFUL. |
| | |
| | 1) NOTE: NOTED FOR INFORMATION. AS THERE ARE SEVERAL |
| | LIGHTING FIXTURES ADDED AND INCLUDING REVISIONS OF THE |
| | TYPES OF LIGHTING FIXTURES, PER FBC 13-415.2, |
| | 13-415.2.ABC.1.1,.1.2, .1.3 AND 13-400.3A COMPLETED |
| | REVISED ENERGY CALCULATIONS WILL BE REQUIRED. THIS |
| | SHOULD BE SUBMITTED ONCE ALL KNOWN COMPONENTS TO |
| | BUILDING ARE COMPLETED. |
| | |
| | 2) NOTE: PLEASE KNOW FOR ITEMS SUCH AS CAMERAS AND |
| | OTHER LOW VOLTAGE WHICH WAS NOT PART OF ORIGINAL PLANS |
| | NEED TO BE PERMITTED. THE VALUE FOR THESE ITEMS IN THE |
| | SCOPE OF WORK NEEDS TO BE APPLIED TO LOW VOLTAGE |
| | PERMITS REQUIRED. |
| | 105.1, 108.3. |
| | NEC 800 |
| | |
| | ** AS OF THIS REVIEW ONLY THE LOW VOLTAGE FOR DATA AND |
| | CATV HAS BEEN APPLIED FOR AND PERMITTED. |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETED LIGHTING CONTROL PANEL |
| | SCHEDULES. FOR EXAMPLE: POOL AREA LIGHTING IS ONE AREA |
| | NOTED WHICH MENTIONS TO WIRE THROUGH LIGHTING CONTROL |
| | PANEL HOWEVER THE PANELS SUBMITTED DO NOT INDICATE |
| | THIS. THIS IS ONE EXAMPLE ONLY.. |
| | 13-415.1.ABC.1.1, .1.2, .1.3. |
| | |
| | 4) NOTE: INFORMATION IS NEEDED FOR NEW WAP ( WIRELESS |
| | ACCESS POINTS) ADDED TO PLANS. THE PLANS SPECIFICALLY |
| | CALL OUT FOR *RECEPTACLES*. THIS LENDS TO THESE BEING |
| | INSTALLED IN THE HALLWAYS WITH EQUIPMENT WHICH WILL BE |
| | PLUGGED IN. THESE WOULD BE REQUIRED TO BE INSTALLED |
| | BELOW THE CEILING HANGING IN THE HALLWAY. |
| | PLEASE SEE 400.8. THE FOLLOWING HAS BEEN EXTRACTED FROM |
| | THE CODE FOR REVIEW. |
| | **400.8 |
| | USES NOT PERMITTED |
| | UNLESS SPECIFICALLY PERMITTED IN 400.7, FLEXIBLE CORDS |
| | AND CABLES SHALL NOT BE USED FOR THE FOLLOWING: |
| | (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A STRUCTURE |
| | (2) WHERE RUN THROUGH HOLES IN WALLS, STRUCTURAL |
| | CEILINGS, SUSPENDED CEILINGS, DROPPED CEILINGS, OR |
| | FLOORS |
| | (3) WHERE RUN THROUGH DOORWAYS, WINDOWS, OR SIMILAR |
| | OPENINGS |
| | (4) WHERE ATTACHED TO BUILDING SURFACES |
| | EXCEPTION TO (4): FLEXIBLE CORD AND CABLE SHALL BE |
| | PERMITTED TO BE ATTACHED TO BUILDING SURFACES IN |
| | ACCORDANCE WITH THE PROVISIONS OF 368.56(B) |
| | SECTION 368.56(B) PROVIDES THE REQUIREMENTS FOR THE |
| | INSTALLATION OF FLEXIBLE CORDS INSTALLED AS BRANCHES |
| | FROM BUSWAYS. |
| | (5) WHERE CONCEALED BY WALLS, FLOORS, OR CEILINGS OR |
| | LOCATED ABOVE SUSPENDED OR DROPPED CEILINGS |
| | (6) WHERE INSTALLED IN RACEWAYS, EXCEPT AS OTHERWISE |
| | PERMITTED IN THIS CODE |
| | THE FLEXIBLE CORDS AND CABLES REFERRED TO IN ARTICLE |
| | 400 ARE NOT LIMITED TO USE WITH PORTABLE EQUIPMENT. |
| | THEY MAY NOT BE USED, HOWEVER, AS A SUBSTITUTE FOR THE |
| | FIXED WIRING OF A STRUCTURE OR WHERE CONCEALED BEHIND |
| | BUILDING WALLS, FLOORS, OR CEILINGS (INCLUDING |
| | STRUCTURAL, SUSPENDED, OR DROPPED-TYPE CEILINGS). SEE |
| | 240.5, 590.4(B), AND 590.4(C) FOR THE USES OF |
| | MULTICONDUCTOR FLEXIBLE CORDS FOR FEEDER AND |
| | BRANCH-CIRCUIT INSTALLATIONS AND FOR OVERCURRENT |
| | PROTECTION REQUIREMENTS FOR FLEXIBLE CORD. SEE 410.30 |
| | FOR CORD-CONNECTED LUMINAIRES. |
| | (7) WHERE SUBJECT TO PHYSICAL DAMAGE |
| | ** |
| | PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT INFORMATION. |
| | |
| | 5) NOTE: PLEASE SEE THE LIGHTING ON PLANS AS NOTED ON * |
| | PROVISO * ISSUED WHEN PERMIT WAS ISSUED HAS NOT BEEN |
| | ADDRESSED. PLEASE SEE E201 AS SOME OF THE LIGHTING |
| | STILL NOT COORDINATE WITH THE LIGHTING ON THE ROOM |
| | LAYOUT PLANS FOR LIGHTING CONTROLS ON E 203,204 ETC. |
| | EXAMPLES ON THREE PREVIOUS REVIEWS WERE GIVEN AND THEY |
| | WILL BE GIVEN AGAIN. SEE KING ACCESSIBLE, AND DOUBLE |
| | QUEEN ACCESSIBLE ETC. |
| | 13-415.1.ABC.1.1, .1.2, .1.3 |
| | FBC 106.1.1 FOR CLARITY, COORDINATION OF PLANS. |
| | *** CALL TO GO OVER THESE AS THEY CAN BE POINTED OUT. |
| | |
| | 6) NOTE: THE FOLLOWING SHEETS SIGNED, DATED AND SEALED |
| | OCT 9TH APPEAR TO BE OK AT THIS TIME HOWEVER BASED ON |
| | THE COMMENTS ABOVE THE OTHER SHEETS IN SETS MAY ALL |
| | NEED REVISIONS. THE FOLLOWING SHEETS IF NO CHANGES ARE |
| | MADE WILL BE STAMPED ONCE RESUBMITTED AND NO |
| | CORRECTIONS ARE NEEDED. |
| | PLEASE CALL TO GO OVER IF NEEDED. NO REVISION FEE WILL |
| | BE CHARGED FOR THESE SHEETS WHEN BRINGING BACK |
| | CORRECTED PLANS AS LONG AS NO CHANGES ARE MADE. |
| | 107A, 107B, 205,301,302, AND 403. THESE SHEETS DO NOT |
| | APPEAR TO NEED REVISIONS AT THIS TIME ALTHOUGH THAT MAY |
| | CHANGE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |