| Plan Review Notes For Permit 08010249 |
| Permit Number |
08010249 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-11-19 16:21:24 | REVISION # 5 | | | | | | 1. ON PAGE E-101 C EXIT SIGNS STILL APOPEAR TO DIRECT | | | PERSONS INTO GARAGE AREA WHICH IS CONSIDERED MORE | | | HAZARDOUS THAN THE AREA THEY ARE EXISTING FROM. PLEASE | | | REMOVE THESE EXIT SIGNS SO PERSONS DO NOT EXIT INTO A | | | MORE HAZARDOUS AREA. | | | | | | 2. THE CARBON MONOXIDE DETECTORS (CO) SHALL BE PROPERLY | | | TESTED WITH CALIBRATION GAS AT THE ESTABLISHED SET | | | POINTS OF THE MANUFACTURER. | | | | | | 3. THE KNOX BOX SHOULD BE INSTALLED NEAR THE MAIN | | | INGRESS/EGRESS DOOR FOR THE HOTEL. | | | | | | 4. CARD READERS OR ANY SECURITY DEVICES SHALL NOT | | | INTERFERE WITH REQUIRED EXITING FROM THE BUILDING. | | | | | | 5. NATURAL GAS INSTALLATION SHALL COMPLY WITH | | | APPROPRIATE NFPA STANDARDS AND RECOGNIZED SAFE | | | PRACTICES. | | | | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | 804-4709 PHONE | | | 804-4774 FAX |
|