| 2008-07-24 16:26:47 | ** PROVISO ** | | | | | | ** PLEASE SEE THE FOLLOWING ITEMS NEED TO BE REVISED | | | AND SUBMITTED FOR REVIEW WITH IN 30DAYS OF ISSUANCE OF | | | PERMIT. IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | 1) NOTE: CARBON MONOXIDE DETECTORS REQUIRED PER RULE | | | 9B-3.0472IN UNITS. | | | | | | 2) NOTE: PLEASE SEE LIGHTING SHOWN AND IDENTIFIED ON | | | SHEET E-201 NEEDS TO COORDINATE WITH THE LIGHTING SHOWN | | | ON GUEST ROOMS. EXAMPLES OF ENLARGED KING, ACCESSIBLE | | | KING AND DOUBLE QUEEN WERE GIVEN ON PREVIOUS REVIEW. | | | PLEASE SEE THE FIXTURES SHOWN ON E-201 ARE WALL SCONCES | | | BASED ON FIXTURE IDENTIFICATION AND FIXTURE LEGEND. THE | | | GUEST ROOM LIGHTING CONTROL PLANS CALL FOR SCONCES IN | | | MANY LOCATIONS FOR GR1, GR2, GR3 ETC HOWEVER PLEASE SEE | | | SOME OF THESE ON THE GUEST ROOM LIGHTING CONTROL PLANS | | | ARE CALLING FOR *LAMPS* WITH SENSORS. TABLE LAMPS WITH | | | SENSORS ARE NOT THE SAME AS WALL SCONCES WITH A | | | LIGHTING CONTROL SYSTEM. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|