| 2009-02-16 10:47:30 | ** DENIED REVIEW ** |
| | |
| | ** REVISIONS |
| | |
| | |
| | 1) NOTE: ALL SUBMITTED REPORTS FOR COORDINATION STUDY |
| | AND SHORT CIRCUIT CALCULATIONS NEED TO BE SIGNED, DATED |
| | AND SEALED BY THE ENGINEER OF RECORD. |
| | FAC 61G15-23.002 |
| | FS 471.023 |
| | |
| | 2) NOTE: THE COORDINATION STUDY NEEDS TO INCLUDE ALL |
| | EQUIPMENT/PANELS/MAIN BREAKERS AND CONDUCTORS FOR LIFE |
| | SAFETY (700 SYSTEMS) AND LEGALLY REQUIRED (701) |
| | SYSTEMS. 700.27,701.18 AND 240.12. THIS IS IMPERATIVE |
| | FOR THESE SYSTEMS TO COORDINATE. AT ANY GIVEN POINT THE |
| | LACK OF COORDINATION COULD RESULT IN A LOSS OF AN |
| | ENTIRE PANEL, MULTIPLE PANELS OR AN ENTIRE EMERGENCY OR |
| | LEGALLY REQUIRED SYSTEM. |
| | PLEASE SEE THE FOLLOWING ITEMS WHICH COULD NOT BE FOUND |
| | IN THE COORDINATION STUDY. THERE WILL BE COMMENTS BELOW |
| | ALSO WITH RESPECT TO THE SHORT CIRCUIT CALCULATIONS AND |
| | ANALYSIS. |
| | |
| | A) PLEASE SEE PANEL ELSW2 IS NOT LOCATED IN THE |
| | COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION |
| | ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION. |
| | |
| | B) PLEASE SEE PANEL EMLW2 IS NOT LOCATED IN THE |
| | COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION |
| | ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION. |
| | |
| | C) PLEASE BE SURE TO INCLUDE THE LARGEST CIRCUIT |
| | CONTRIBUTION IS INCLUDED ON BOTH OF THESE PANELS. |
| | |
| | D) MSB IS NOTED AS MDP. (SAME HOWEVER ONLY MISPRINTED |
| | FOR IDENTIFICATION). |
| | |
| | E) PLEASE INCLUDE CONDUCTOR CONTRIBUTION FOR ALL |
| | EQUIPMENT. THE CONDUCTORS ARE NOTED FOR EDPLS, TLSE2 |
| | FEEDER, CONDUCTORS FOR ELSE2 AND FIRE PUMP. HOWEVER |
| | WHERE ARE THE OTHERS? |
| | |
| | F) PLEASE ALSO SEE MISSING TLSW-2. |
| | |
| | 3) NOTE: PLEASE BE SURE THE SHORT CIRCUIT CALCULATIONS |
| | SCHEDULE ALSO COORDINATES WITH THE IDENTIFICATION OF |
| | ALL EQUIPMENT ON THE STUDY AND THE PLANS. THE SHORT |
| | CIRCUIT CALCULATIONS WILL BE NOTED AS SCC FOR THE |
| | REMAINDER OF THESE COMMENTS. SAME CODE SECTIONS AS |
| | NOTED ABOVE. |
| | |
| | FOR EXAMPLE: THE LIST OF PANELS AND EQUIPMENT ON THE |
| | THIRD PAGE OF THE SCC IN INDICATES AN ELSE3, YET THERE |
| | IS NO SUCH EQUIPMENT NOTED ON PLANS OR COORDINATION |
| | STUDY. |
| | THE RISER AT THE BACK OF THE SCC ALSO DOES NOT INCLUDE |
| | THIS ELSE3 PANEL. IF THIS IS REALLY THE ELSW2 PANEL, |
| | PLEASE ADJUST BOTH THE SCC AND THE SCC RISER. |
| | |
| | FOR EXAMPLE: THE LIST ON THIS SAME PAGE THREE OF THE |
| | SCC DOES NOT LIST EMLW2. THE RISER ON THE BACK OF THE |
| | SCC DOES INCLUDE THIS EMLW2 PANEL. |
| | |
| | |
| | **THE COMMENTS ABOVE IN NOTE #2 ALREADY GIVE THE NOTE |
| | WITH RESPECT TO THE COORDINATION STUDY MISSING THE |
| | ELSW2 AND EMLW2. |
| | |
| | 4) NOTE: PLEASE IDENTIFY RECEPTACLES NOTED ON PANEL |
| | SCHEDULE EMLW2 FOR CIRCUITS 15, 17 /19. THE SCHEDULE |
| | INDICATES REC HOWEVER THE INFORMATION ON THE RISER |
| | ACTUALLY SHOWS THESE AS CIRCUITS TO THE GENERATOR. THE |
| | OCP FOR CIRCUIT 17/19 SEEMS TO BE A LARGER BREAKER OR |
| | CIRCUIT WHICH WILL BE A REVISED PORTION OF THE STUDY. |
| | THIS NEEDS TO BE VERIFIED BEFORE REVISED THE |
| | COORDINATION STUDY. |
| | 408.4 |
| | FBC 106.1.1, 106.5 FOR CLARITY, COORDINATION OF RECORD |
| | PLANS. |
| | |
| | 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL |
| | CHANGES WITH RESPECT TO PLANS FROM AIC RATINGS, |
| | CONDUCTORS ETC FROM PREVIOUS PLANS A NEW ELECTRICAL |
| | INSPECTION WILL BE REQUIRED BEFORE THE TCO. |
| | |
| | |
| | 6) NOTE: SHEETS E-102A, 102B, 103A ,203 AND 204 ARE OK. |
| | THESE SHEETS RETAINED FOR FILE. |
| | THE OTHER SHEETS SUCH AS RISER, AND PANEL SCHEDULE |
| | SHEETS NEED TO BE BROUGHT BACK IN IF THEY ARE NOT |
| | REVISED. |
| | |
| | *** ALL COMMENTS WERE GONE OVER WITH THE ENGINEER OF |
| | RECORD. THE ORIGINAL COMMENTS E-MAILED TO THE ENGINEER |
| | HAVE BEEN ADJUSTED FOR THESE POSTED NOTES. ONE COMMENT |
| | WAS REMOVED AS THE PRINTED SHEET WAS NOT EASILY |
| | READABLE AND ENGINEER CLARIFIED INFORMATION. THE |
| | COMMENT #4 ABOVE WAS REVISED ALSO FOR MORE INFORMATION |
| | AND COORDINATION NEEDED. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |