| Date |
Text |
| 2008-07-03 11:08:29 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DESIGN MANUAL |
| | CITY WPB MUNICIPAL CODES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | |
| | 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02 |
| | GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING |
| | TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF. |
| | INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW |
| | METHOD. SECTIONS 106.1.2 & 608. |
| | ****RESPONSE NOTED, BUT THE 950XLU IS REQUIRED TO BE A |
| | MAXIMUM 30" ABOVE THE FLOOR WITH AN INDIRECT WASTE |
| | RECEPTOR, NOT IN THE CEILING AS SHOWN. THIS IS REQUIRED |
| | FOR SERVICING AND TESTING. THE REQUIREMENT FOR BACKFLOW |
| | PREVENTION CAN BE ACHIEVED WITH A "WATTS N36 VACUUM |
| | BREAKER OR EQUIALENT AT THE TOP OF THE DROP TO THE |
| | DRYERS. |
| | ******RESPONSE NOTED, BUT THE 950XLU BACKFLOW PREVENTOR |
| | IS STILL SHOWN ON SHEETS P203A & P-504. PLEASE SHOW THE |
| | N36 VACUUM BREAKER. |
| | |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | 34. OK |
| | 35. OK |
| | 36. OK |
| | 37. OK |
| | 38. OK |
| | 38A. OK |
| | 39. OK |
| | 40 OK |
| | 41. OK |
| | 42. OK |
| | 43. OK |
| | 44. OK |
| | 45. OK |
| | 46. OK |
| | 47. OK |
| | 48. OK |
| | 49. OK |
| | 50. OK |
| | 51. OK |
| | |
| | 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK |
| | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER |
| | SECTION 903.4. |
| | ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT |
| | STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK |
| | ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE |
| | DRAINAGE STACKS. |
| | ******RESPONSE NOTED, BUT RISER "I" DOES NOT SHOW THE |
| | BENT FROM THE 2ND FLOOR OR CONNECTION TO THE SANITARY |
| | STACK. (SHT 502). |
| | |
| | 53. OK |
| | 54. OK |
| | 55. OK |
| | 56. OK |
| | 57. OK |
| | 58. OK |
| | 59. OK |
| | 60. OK |
| | 61. OK |
| | 62. OK |
| | 63. OK |
| | 64. OK |
| | 65. OK |
| | 66. OK |
| | 67. OK |
| | 68. OK |
| | 69. OK |
| | 70. OK |
| | 71. OK |
| | 72. OK |
| | 73. OK |
| | 74. OK |
| | 75. OK |
| | 76. OK |
| | 77. OK |
| | |
| | 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12 |
| | DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT COMMENT STILL NOT ADDRESSED. |
| | BRANCH LINE SHOWN UPSTREAM OF CONDENSATE CONNECTION AND |
| | ST13 ON SHT P-101A. PLEASE CORRELATE. |
| | |
| | 79. OK |
| | 80. OK |
| | 81. OK |
| | 82. OK |
| | 83. OK |
| | 84. OK |
| | 85. OK |
| | 86. OK |
| | 87. OK |
| | 88. OK |
| | 89. OK |
| | |
| | 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | F. OK |
| | G. OK |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT |
| | SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS |
| | APPLICATION IS APPLIED FOR). |
| | |
| | I. N/A |
| | J. N/A |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | |
| | ***********NEW COMMENT*********** |
| | |
| | 1C. SHT P-602 SHOWS THE REGULATORS TO BE FISHER MODEL |
| | Y600A BUT THE MANUF SPECIFICATIONS FOR THE REGULATORS |
| | INDICATE THE REGULATORS TO MODEL S300 SERIES. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED |
| | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL |
| | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |