| 2008-06-30 15:23:07 | ** DENIED THIRD REVIEW ** |
| | |
| | PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEWS ARE |
| | IN NEED OF ADDRESSING. |
| | PLEASE SEE SOME COORDINATION OF OTHER COMMENTS BELOW |
| | WITH SUPPORTING DOCUMENTS. |
| | |
| | 1) NOTE: THE PREVIOUS REVIEWS REQUESTED FOR SUBMITTALS |
| | OF MANUFACTURES SPECS/CUT SHEETS FOR THE ATS, |
| | GENERATOR, FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | THE RESPONSE MENTIONS TO SEE SPECS IN THE SUBMITTAL |
| | BOOKS. PLEASE BE SURE TO COORDINATE SUBMITTALS. FOR |
| | EXAMPLE: |
| | PLEASE SEE THERE ARE TWO SUBMITTALS FOR FIRE PUMP: ONE |
| | SHOWS AURORA, THE OTHER SHOWS MORSE FAIRBANKS. PLEASE |
| | SEE THERE ARE TWO SUBMITTALS FOR THE FIRE PUMP |
| | CONTROLLER: ONE SHOWS METRON WHICH DOES NOT INDICATE |
| | ANY LISTING AND THE OTHER IS A HUBBELL FOR FIRE PUMP |
| | AND JOCKEY PUMP WHICH DOES SHOW LISTING. |
| | PLEASE SEE THE ATS SPECS: ONE SHOWS AN ASCO AND THE |
| | OTHER A CATERPILLAR. |
| | PLEASE SEE THE GENERATOR SPACES: ONE SHOWS AN ONAN AND |
| | THE OTHER A CATERPILLAR. |
| | |
| | ** PLEASE REMOVE THE DOCUMENTS FORREVIEW AND RECORD |
| | PLANS. PLEASE BE SURE THE FINAL SPECS DO CONTAIN THE |
| | LISTING. IF THIS WERE THE ONLY COMMENT A REPRESENTATIVE |
| | WOULD BE ABLE TO CORRECT IN OFFICE. |
| | 110.3, 90.7, 695 OF NFPA-70, CHAPTER 9 AND 10. |
| | FBC 106.1.1 FOR CLARITY OF CONSTRUCTION DOCUMENTS. |
| | |
| | 2) NOTE: PLEASE SEE THE SUBMITTED COORDINATION STUDY |
| | WHICH WAS PREVIOUSLY REQUESTED. THE INFORMATION ON THE |
| | STUDY DOES NOT COORDINATE WITH THE SUBMITTED ELECTRICAL |
| | PLANS. PLEASE SEE SOME EXAMPLES GIVEN. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE RISER WHICH SHOWS 1-SET OF 3/0 FROM |
| | GENERATOR TO FIRE PUMP YET THE COORDINATION STUDY SHOWS |
| | 2-SETS OF 4/0. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE RISER SHOWS 225 FOR ATS-LS, YET THE |
| | COORDINATION STUDY SHOWS 250AMPS. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THERE IS NO NORMAL FEED TO THE FIRE PUMP. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE BREAKER OR RISER FOR FIRE PUMP ON THE |
| | GENERATOR IS SHOWN AS 450AMPS, YET THE COORDINATION |
| | STUDY SHOWS BREAKER AT 600AMPS. |
| | |
| | ** THESE ARE SOME EXAMPLES. |
| | |
| | ** PLEASE BE AWARE THAT THESE MUST BE SIGNED, DATED AND |
| | SEALED BY THE DESIGNER OF RECORD. THESE WERE NOT |
| | SIGNED, DATED OR SEALED. |
| | FAC61G15-23.002, 61G15-33.0002, FS 471.025 |
| | NEC 240.12 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | *MINIMUM* LIGHTING REQUIRED FOR LIFE SAFETY. PLEASE SEE |
| | NFPA-101 7.8.1.3, 7.8, 7.9, 7.9.2 |
| | AS THE MINIMUM LEVELS FOR WALK AREAS (NOT STAIRS) IS |
| | REQUIRED TO BE 1FT CANDLE UNDER NORMAL AS WELL AS 1FT |
| | CANDLE UNDER EMERGENCY. THERE ARE SOME EXAMPLES GIVEN |
| | WHICH THE LIGHTING LEVELS ARE AS LOW HALF THE *MINIMUM* |
| | REQUIRED BY THE LIFE SAFETY CODE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE E-101C AND E-101D CORRIDOR #149 WHICH SHOWS |
| | .04 FT CANDLES YET THE MINIMUM NEEDS TO BE A MINIMUM OF |
| | 1FT CANDLE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE 603C, 603DAS THE LIGHTING IN AREAS 237, |
| | 242 AND 230 ARE ALL BELOW THE 1FT CANDLE MINIMUM FOR |
| | EMERGENCY EGRESS. THESE LEVELS ARE SHOWN AS .5 IN |
| | CORRIDOR 237, .5 IN CORRIDOR 242 AND .6 INEGRESS PATH |
| | 230. |
| | |
| | ** THESE ARE EXAMPLES GIVEN AS A BENEFIT TO DESIGN |
| | TEAM. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH |
| | RESPECT TO ALL LIGHTING ON PLANS AND THE NEED FOR |
| | COORDINATION WITH THE SUBMITTED FLA-COM ENERGY |
| | CALCULATIONS. |
| | PLEASE SEE SECTIONS, 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| | AND .1.3. |
| | THIS IS TO INCLUDE ALL INTERIOR AND EXTERIOR LIGHTING. |
| | SOME EXAMPLES WILL BE GIVEN BELOW. THESE ARE GIVEN AS A |
| | BENEFIT ONLY. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE EXTERIOR LIGHTS SUCH AS THE *M* FIXTURES |
| | SHOWN ON PLANS ON THE SOUTH SIDEWALK YET THESE ARE NOT |
| | IN ANY EXTERIOR OR INTERIOR LIGHTING IN THE INPUT DATA |
| | REPORTS. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE INTERIOR ELEVATOR LOBBY MISSING THE SAS |
| | FIXTURE IN THE IDR. PLEASE ALSO SEE THE SAME ARE FOR |
| | THE *SP* FIXTURE COUNT. |
| | ** THIS SAME AREA ON THE METHOD OF CONTROLS INDICATES |
| | OCCUPANCY SENSORS YET NO OCCUPANCY SENSORS ARE SHOWN ON |
| | PLANS. THIS APPEARS TO BE AN ERROR IN THE CHOICE OF |
| | LIGHTING CONTROLS OPTION. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE INTERIOR LIGHTING IN THE GUEST ROOMS |
| | NEED TO COORDINATE WITH THE INPUT DATA REPORT. THE |
| | LIGHTING PLANS ON E-201 AND E-205 ARE NOT THE SAME. IN |
| | FACT SOME EXAMPLES OF THIS WILL BE GIVEN. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE KING SUITES.E-201 SHOWS A TOTAL OF 11 |
| | FIXTURES YET THE OTHER LIGHTING PLANS FOR CONTROLS ON |
| | E-205 SHOW ONLY 8 FIXTURES. |
| | IN EITHER CASE THE IDR OF THE SUBMITTED ENERGY |
| | CALCULATIONS ONLY SHOW 7 FIXTURES. |
| | ** PLEASE LOOK AT LIGHTING PLANS FOR TYPES OF FIXTURES |
| | AS THERE IS THE DIFFERENCE OF 4 FIXTURES IN EACH OF |
| | THESE ALONE. |
| | COORDINATE TYPES OF FIXTURES. (WALL SCONCES ETC) |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE ENLARGED KING ACCESSIBLE UNIT: THIS |
| | SHOWS DIFFERENT FIXTURES ON E-201 COMPARED TO FIXTURES |
| | ON E-205. ALL OF THESE UNITS ALSO SHOW A LOWER NUMBER |
| | OF FIXTURES ON THE IDR. IT IS NOT JUST ONE FIXTURE |
| | TOTAL, IT IS ONE FIXTURE FOR EACH UNIT. |
| | ** PLEASE ALSO COORDINATE TYPES OF FIXTURES. (WALL |
| | SCONCES) |
| | |
| | ** THESE WERE S FEW EXAMPLES GIVEN AS A BENEFIT TO |
| | DESIGN TEAM. THIS IS NOT ALL FIXTURES AS THERE ARE |
| | OTHERS FOR OTHER UNITS WHICH E201 DOES NOT COORDINATE |
| | WITH E-205. |
| | |
| | 5) NOTE: PLEASE BE AWARE OF NEW FLORIDA ADMINISTRATIVE |
| | CODE RULE 9B-3.0472. THIS REQUIRES ALL BUILDING PERMITS |
| | ISSUED AFTER JULY 1ST TO CONTAIN CO SENSORS WHEN |
| | MEETING THE PROVISIONS AND DEFINITIONS AS FOLLOWS. |
| | PLEASE SEE THIS RULING BECAME IN AFFECT AFTER ADOPTION |
| | OF FS 553.885. |
| | ** THIS CAN BE A PROVISO TO ADJUST ALL DEVICES ON PLANS |
| | HOWEVER PLANS ARE GOING BACK FOR CORRECTIONS AT THIS |
| | TIME. |
| | |
| | |
| | ********** |
| | |
| | (1) DEFINITIONS: FORPURPOSES OF THIS RULE, THE |
| | FOLLOWING DEFINITIONS SHALL APPLY: |
| | (A) CARBON MONOXIDE ALARM. A DEVICE FOR THEPURPOSE OF |
| | DETECTING CARBON MONOXIDE, THAT PRODUCES A DISTINCT |
| | AUDIBLE ALARM,AND IS LISTED OR LABELED WITH THE |
| | APPROPRIATE STANDARD, EITHER ANSI/UL 2034 -96, |
| | STANDARD FOR SINGLE AND MULTIPLE STATION CO ALARMS, |
| | INCORPORATED HEREIN BYREFERENCE, OR UL 2075 - 04, GAS |
| | AND VAPOR DETECTOR SENSOR, INCORPORATED HEREINBY |
| | REFERENCE, IN ACCORDANCE WITH ITS APPLICATION. BOTH |
| | DOCUMENTS MAY BE OBTAINEDBY WRITING TO: CODES AND |
| | STANDARDS SECTION, DEPARTMENT OF COMMUNITY AFFAIRS, |
| | 2555 SHUMARD OAK BOULEVARD, TALLAHASSEE, FLORIDA |
| | 32399-2100. |
| | |
| | (B) FOSSIL FUEL. COAL, KEROSENE,OIL, FUEL GASES, OR |
| | OTHER PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS |
| | CARBONMONOXIDE AS A BY-PRODUCT OF COMBUSTION. |
| | |
| | (2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| | FOSSIL-FUEL-BURNINGHEATER OR APPLIANCE, A FIREPLACE, |
| | OR AN ATTACHED GARAGE SHALL HAVE ANOPERATIONAL CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FORSLEEPING PURPOSES. |
| | |
| | (3) IN NEWCONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| | PRIMARY POWER FROM THE BUILDING WIRINGWHEN SUCH |
| | WIRING IS SERVED FROM THE LOCAL POWER UTILITY. SUCH |
| | ALARMS SHALL HAVEBATTERY BACK UP. |
| | |
| | (4)COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY ANATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| | HISTORY,NEW 11-18-07. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |