| 2009-01-31 12:01:03 | *** DENIED*** |
| | |
| | |
| | 1) NOTE: THE LOCATION NOTES OF T-STAT DEVICE E528 ON |
| | ENLARGE GUEST ROOM LIGHTING CONTROLS PLANS NEED TO BE |
| | UPDATED OR REMOVED. THE NOTES STATE THE DEVICE BY THE |
| | DOOR DOES NOT PROVIDE COVERAGE AND NOTES AN ADDITIONAL |
| | DEVICE IS NEEDED FOR FULL COVERAGE. AFTER A PHONE |
| | MEETING WITH ELECTRICAL DESIGNERS AS WELL AS THE |
| | LIGHTING SYSTEM MANUFACTURE IT WAS STATED THE SWITCH |
| | DEVICES AT BED LOCATIONS ALSO ACT AS AN OVER RIDE |
| | WHETHER OR NOT THE T-STAT/E528 DEVICE SENSES AN |
| | OCCUPANT OR NOT. |
| | THE NOTES ON THESE SHEETS WILL BE UPDATED. |
| | 13-415.1.ABC.1, NFPA-101 7.8 |
| | |
| | 2) NOTE: AS NOTED ON PREVIOUS SUBMITTAL REVIEW OF POOL |
| | HEATER THIS UNIT IS NOT LISTED ON THE INPUT DATA REPORT |
| | OF THE SUBMITTED CALCULATIONS. |
| | 13-412, 13-400.A.3 |
| | THERE ARE OTHER ITEMS WITH THE SUBMITTED CALCULATIONS |
| | WHICH ARE NOT COORDINATING WITH PLANS. FIXTURE TYPE T |
| | APPEARS TO BE OVER ALONG WITH M HOWEVER OTHER FIXTURES |
| | AS R/RE APPEAR TO BE A LITTLE UNDER. |
| | PLEASE VERIFY EXTERIOR LIGHTING AS INSTALLED IN THE |
| | FIELD WITH WHAT IS SHOWN ON PLANS AND IN THE |
| | IDR.13-415.2.ABC.1.3 |
| | |
| | 3) NOTE: AS NOTED IN PREVIOUS SUBMITTED THERE ARE NOTES |
| | PERTAINING TO THE AIC RATINGS OF SOME PANELS/BREAKERS |
| | INSTALLED AND NOTED ON SHOP DRAWINGS. THESE ITEMS NEED |
| | TO BE CONFIRMED THEY HAVE BEEN CORRECTED AND NOT |
| | CHANGED ANY BREAKERS ETC FROM THE PREVIOUS COORDINATION |
| | STUDY SUBMITTED. |
| | ANY CHANGES WITH A LOWER RATING WHICH WOULD AFFECT THE |
| | COORDINATION OF ANY LIFE SAFETY OR LEGALLY REQUIRED |
| | SYSTEM WOULD NEED TO BE ADDRESSED AT THIS TIME. |
| | 240.12, 700.27, 701.18 |
| | |
| | 4) NOTE: THE FIXTURE ON THE SECOND LEVEL PARAPET WALL |
| | MAY BE OVER THE ACTUAL PROPERTY LINE IF MOUNTED ON THE |
| | NORTH WALL. PLEASE VERIFY. |
| | |
| | 5) NOTE: PLEASE BE SURE TO REVISE ALL CIRCUITING, |
| | EQUIPMENT AND ITEMS ADDED FOR POOL PANEL. AN EXAMPLE IS |
| | THE NEW SUBMITTAL FOR ELECTRIC POOL HEATER WHICH IS NOT |
| | ON PANEL PL. |
| | PLEASE REVISE ALL LOADS ETC. |
| | 220,408,310.16,240.4 ETC |
| | FBC 106.5, 106.1.1 FOR COORDINATION AND CLARITY OF |
| | RECORD PLANS. |
| | |
| | |
| | |
| | ** ONCE NOTES FOR SUBMITTALS AND ITEMS ABOVE HAVE BEEN |
| | ADDRESSED SOME SHEETS IN SETS MAY NOT NEED TO BE |
| | REVISED. SHEETS WHICH DO NOT NEED REVISIONS SHOULD BE |
| | BROUGHT BACK IN WITH OTHER REVISED ITEMS. |
| | |
| | |
| | FBC 106.1.1 FOR COORDINATION AND CLARITY WITH PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |