Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop E
Sequence Number 28
Notes
Date Text
2009-01-31 12:01:03*** DENIED***
  
  
 1) NOTE: THE LOCATION NOTES OF T-STAT DEVICE E528 ON
 ENLARGE GUEST ROOM LIGHTING CONTROLS PLANS NEED TO BE
 UPDATED OR REMOVED. THE NOTES STATE THE DEVICE BY THE
 DOOR DOES NOT PROVIDE COVERAGE AND NOTES AN ADDITIONAL
 DEVICE IS NEEDED FOR FULL COVERAGE. AFTER A PHONE
 MEETING WITH ELECTRICAL DESIGNERS AS WELL AS THE
 LIGHTING SYSTEM MANUFACTURE IT WAS STATED THE SWITCH
 DEVICES AT BED LOCATIONS ALSO ACT AS AN OVER RIDE
 WHETHER OR NOT THE T-STAT/E528 DEVICE SENSES AN
 OCCUPANT OR NOT.
 THE NOTES ON THESE SHEETS WILL BE UPDATED.
 13-415.1.ABC.1, NFPA-101 7.8
  
 2) NOTE: AS NOTED ON PREVIOUS SUBMITTAL REVIEW OF POOL
 HEATER THIS UNIT IS NOT LISTED ON THE INPUT DATA REPORT
 OF THE SUBMITTED CALCULATIONS.
 13-412, 13-400.A.3
 THERE ARE OTHER ITEMS WITH THE SUBMITTED CALCULATIONS
 WHICH ARE NOT COORDINATING WITH PLANS. FIXTURE TYPE T
 APPEARS TO BE OVER ALONG WITH M HOWEVER OTHER FIXTURES
 AS R/RE APPEAR TO BE A LITTLE UNDER.
 PLEASE VERIFY EXTERIOR LIGHTING AS INSTALLED IN THE
 FIELD WITH WHAT IS SHOWN ON PLANS AND IN THE
 IDR.13-415.2.ABC.1.3
  
 3) NOTE: AS NOTED IN PREVIOUS SUBMITTED THERE ARE NOTES
 PERTAINING TO THE AIC RATINGS OF SOME PANELS/BREAKERS
 INSTALLED AND NOTED ON SHOP DRAWINGS. THESE ITEMS NEED
 TO BE CONFIRMED THEY HAVE BEEN CORRECTED AND NOT
 CHANGED ANY BREAKERS ETC FROM THE PREVIOUS COORDINATION
 STUDY SUBMITTED.
 ANY CHANGES WITH A LOWER RATING WHICH WOULD AFFECT THE
 COORDINATION OF ANY LIFE SAFETY OR LEGALLY REQUIRED
 SYSTEM WOULD NEED TO BE ADDRESSED AT THIS TIME.
 240.12, 700.27, 701.18
  
 4) NOTE: THE FIXTURE ON THE SECOND LEVEL PARAPET WALL
 MAY BE OVER THE ACTUAL PROPERTY LINE IF MOUNTED ON THE
 NORTH WALL. PLEASE VERIFY.
  
 5) NOTE: PLEASE BE SURE TO REVISE ALL CIRCUITING,
 EQUIPMENT AND ITEMS ADDED FOR POOL PANEL. AN EXAMPLE IS
 THE NEW SUBMITTAL FOR ELECTRIC POOL HEATER WHICH IS NOT
 ON PANEL PL.
 PLEASE REVISE ALL LOADS ETC.
 220,408,310.16,240.4 ETC
 FBC 106.5, 106.1.1 FOR COORDINATION AND CLARITY OF
 RECORD PLANS.
  
  
  
 ** ONCE NOTES FOR SUBMITTALS AND ITEMS ABOVE HAVE BEEN
 ADDRESSED SOME SHEETS IN SETS MAY NOT NEED TO BE
 REVISED. SHEETS WHICH DO NOT NEED REVISIONS SHOULD BE
 BROUGHT BACK IN WITH OTHER REVISED ITEMS.
  
  
 FBC 106.1.1 FOR COORDINATION AND CLARITY WITH PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  