| | WINDOW SHOP DRAWING REVIEW: |
| | ACTION: DENIED |
| | |
| | 1) SHEET 9 OF 12 |
| | A) W2- NOTE DETAIL4/10 INDICATES NO ANCHORS REQUIREDAT |
| | CONTINIOUS JAMB WHERE AS DETAIL INDICATES ANCHOR |
| | SPACING ON SIDE JAMBS. DISCREPANCY 106.1.2 ADDITIONAL |
| | INFORMATION 1609..6 |
| | |
| | B) W-2 ALSO INDICATS THAT THE JAMBS & MULLION ARE NOT |
| | REINFORCED, THE TRIBUTARY AREA FOR THE HORIZONTAL |
| | MULLION IS ROUGHLY 46.5"X72" SHEET 3 OF 7 MULLIONS W/O |
| | REINFORCEMENT INDICATE A -80.0 WHERE AS |
| | THE WINDOW INDICATES A NEGATIVE 89. |
| | |
| | C) W-2A IS THE SAME SIZE WINDOW WITH THE SAME SITUATION |
| | AS THE W-2 WINDOW. |
| | |
| | D) W-3A NO DESIGNATION AS TO MUTTINS. |
| | |
| | E) W-3A THE JAMB AND MULLION DETAIL INDICATES |
| | NON-REINFORCED WITH LOW PRESSURES FROM NOA SHEET 3 OF |
| | 7.UN-REINFORCED JAMBS AND MULLIONS ARE GOOD TO 80 PSF |
| | THIS WINDOW IS INDICATED AS A -89.LOW PRESSURE |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |